[Federal Register Volume 90, Number 45 (Monday, March 10, 2025)]
[Notices]
[Pages 11628-11630]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 2025-03762]


=======================================================================
-----------------------------------------------------------------------

NUCLEAR REGULATORY COMMISSION

[Docket Nos. 72-1036, 50-220, and 50-410; CEQ ID EAXX-429-00-000-
1740728721; NRC-2025-0030]


Constellation Energy Generation, LLC; Nine Mile Point Nuclear 
Station Units 1 and 2; Independent Spent Fuel Storage Installation; 
Environmental Assessment and Finding of No Significant Impact

AGENCY: Nuclear Regulatory Commission.

ACTION: Notice; issuance.

-----------------------------------------------------------------------

SUMMARY: The U.S. Nuclear Regulatory Commission (NRC) is issuing an 
environmental assessment (EA) and a finding of no significant impact 
(FONSI) for an exemption request submitted by Constellation Energy 
Generation, LLC (CEG) that would permit Nine Mile Point Nuclear Station 
(NMP) Units 1 and 2 to load six 89 multi-purpose canisters (MPC) at the 
NMP independent spent fuel storage installation (ISFSI) in a near-term 
loading campaign beginning in May 2025, including the use of the HI-
TRAC VW transfer cask (HI-TRAC) during loading and transport 
operations, where the terms, conditions, and specifications in 
Certificate of Compliance (CoC) No. 1032, Amendment No. 3, Revision No. 
0, are not met.

DATES: The EA and FONSI referenced in this document are available on 
March 10, 2025.

ADDRESSES: Please refer to Docket ID NRC-2025-0030 when contacting the 
NRC about the availability of information regarding this document. You 
may obtain publicly available information related to this document 
using any of the following methods:
     Federal Rulemaking Website: Go to https://www.regulations.gov and search for Docket ID NRC-2025-0030. Address 
questions about Docket IDs in Regulations.gov to Bridget Curran; 
telephone: 301-415-1003; email: [email protected]. For technical 
questions, contact the individual listed in the For Further Information 
Contact section of this document.
     NRC's Agencywide Documents Access and Management System 
(ADAMS): You may obtain publicly available documents online in the 
ADAMS Public Documents collection at https://www.nrc.gov/reading-rm/adams.html. To begin the search, select ``Begin Web-based ADAMS 
Search.'' For problems with ADAMS, please contact the NRC's Public 
Document Room (PDR) reference staff at 1-800-397-4209, at 301-415-4737, 
or by email to [email protected]. For the convenience of the reader, 
instructions about obtaining materials referenced in this document are 
provided in the ``Availability of Documents'' section.
     NRC's PDR: The PDR, where you may examine and order copies 
of publicly available documents, is open by appointment. To make an 
appointment to visit the PDR, please send an email to 
[email protected] or call 1-800-397-4209 or 301-415-4737, between 8 
a.m. and 4 p.m. eastern time (ET), Monday through Friday, except 
Federal holidays.

FOR FURTHER INFORMATION CONTACT: Yen-Ju Chen, Office of Nuclear 
Material Safety and Safeguards, U.S. Nuclear Regulatory Commission, 
Washington, DC 20555; telephone: 301-415-1018; email: [email protected].

SUPPLEMENTARY INFORMATION:

I. Introduction

    The NRC is reviewing an exemption request from CEG, dated January 
22, 2025, and supplemented on February 4, 2025. CEG is requesting an 
exemption, pursuant to section 72.7 of title 10 of the Code of Federal 
Regulations (10 CFR), in paragraphs 72.212(a)(2), 72.212(b)(3), 
72.212(b)(5)(i), 72.212(b)(11), and 72.214 that require CEG to comply 
with the terms, conditions, and specifications of the CoC No. 1032, 
Amendment No. 3, Revision No. 0. If approved, the exemption would allow 
CEG to use the HI-STORM Flood/Wind (FW) MPC Storage System, including 
the use of the HI-TRAC during loading and transport operations, for six 
specific MPCs (i.e., MPC-89) at the NMP ISFSI, beginning in May 2025, 
where the terms, conditions, and specifications in CoC No. 1032, 
Amendment No. 3, Revision No. 0, are not met.

II. Environmental Assessment

Background

    NMP is located on the southeastern shore of Lake Ontario, 
approximately 8 kilometers (5 miles) northeast of Oswego, New York, and 
60 kilometers (36 miles) north-northwest of Syracuse, New York. Unit 1 
began operating in 1969 and Unit 2 began operating in 1988. CEG has 
been storing spent fuel in the NMP ISFSI under a general license as 
authorized by 10 CFR part 72, subpart K, ``General License for Storage 
of Spent Fuel at Power Reactor Sites.'' CEG currently uses the HI-STORM 
FW MPC Storage System under CoC No. 1032, Amendment No. 3, Revision No. 
0, for dry storage of spent nuclear fuel in a specific MPC (i.e., MPC-
89) at the NMP ISFSI.

Description of the Proposed Action

    The CoC is the NRC-approved design for each dry cask storage 
system. The proposed action would exempt the applicant from the 
requirements of 10 CFR 72.212(a)(2), 72.212(b)(3), 72.212(b)(5)(i), 
72.212(b)(11), and 72.214 only as these requirements pertain to the use 
of the six MPC-89 in the HI-STORM FW MPC Storage System planned for a 
near-term loading campaign beginning in May 2025. The exemption would 
allow CEG to use the HI-STORM FW MPC Storage System, including the use 
of the HI-TRAC during loading and transport operations, for six MPC-89 
at the NMP ISFSI, beginning in May 2025, despite CEG's site-specific 
analysis of a postulated tornado missile event for the HI-TRAC not 
being in compliance with the terms, conditions, and specifications in 
the CoC No. 1032, Amendment No. 3, Revision No. 0.
    Before using a CoC, general licensees are required to perform a 
site-specific evaluation to establish that, once loaded with spent 
fuel, the cask will conform to the terms, conditions, and 
specifications of the CoC, including following the NRC-approved final 
safety analysis report (FSAR) methodology. CEG currently uses the HI-
STORM FW

[[Page 11629]]

MPC Storage System under CoC No. 1032, Amendment No. 3, Revision No. 0, 
for dry storage of spent nuclear fuel in MPC-89 at the NMP ISFSI. The 
HI-STORM FW MPC Storage System CoC provides the requirements, 
conditions, and operating limits necessary for use of the system to 
store spent fuel. One of the operating limits established in the CoC 
involves potential tornado-generated missile impacts. The HI-STORM FW 
FSAR table 2.2.5 evaluates a generic set of tornado-generated missile 
impacts. CEG discovered that NMP's site-specific analysis performed to 
demonstrate protection of the loaded MPC-89, while in the HI-TRAC, 
against tornado-generated missiles was not performed consistent with 
the NRC-approved method of evaluation in the FSAR. Contrary to CEG's 
site-specific analysis, the NRC-approved evaluation in the FSAR does 
not take credit for the missile resistance offered by the HI-TRAC water 
jacket shell, and assumes that the small and intermediate missiles will 
penetrate the water jacket shell with no energy loss.
    Therefore, CEG requests this exemption to allow it to conduct the 
planned loading and transport operations of the six MPC-89 in the HI-
STORM FW MPC Storage System at NMP ISFSI beginning in May 2025, even 
though, because of the different tornado-generated missile analysis of 
the HI-TRAC in NMP's site-specific review, the terms, conditions, and 
specifications of the CoC will not be met.

Need for the Proposed Action

    CEG requested this exemption in order to allow the use of the HI-
STORM FW MPC Storage System, including the use of the HI-TRAC during 
loading and transport operations for six MPC-89 at the NMP ISFSI, 
beginning in May 2025, despite the terms, conditions, and 
specifications of the CoC not being met. Approval of the exemption 
request would allow CEG to effectively manage the margin to full core 
discharge capacity to enable refueling and offloading fuel from the 
reactor. It would also allow CEG to effectively manage the availability 
of the specialized resources and equipment needed to support competing 
fuel loading and operational activities at NMP.

Environmental Impacts of the Proposed Action

    This EA evaluates the potential environmental impacts of granting 
an exemption from the terms, conditions, and specifications in CoC No. 
1032, Amendment No. 3, Revision No. 0. The exemption would allow CEG to 
use the HI-STORM FW MPC Storage System, including the use of the HI-
TRAC during loading and transport operations for six MPC-89 at the NMP 
ISFSI, for the loading campaign beginning in May 2025, even though the 
terms, conditions, and specifications of the CoC will not be met.
    The potential environmental impacts of storing spent nuclear fuel 
in NRC-approved storage systems have been documented in previous 
assessments. On July 18, 1990 (55 FR 29181), the NRC amended 10 CFR 
part 72 to provide for the storage of spent fuel under a general 
license in cask designs approved by the NRC. The EA for the 1990 final 
rule analyzed the potential environmental impacts of using NRC-approved 
storage casks. The EA for the HI-STORM FW MPC Storage System, CoC No. 
1032, Amendment No. 3, Revision No. 0, (82 FR 29225), published in 
2017, tiers off of the EA issued for the July 18, 1990, final rule. 
``Tiering'' off earlier EAs is a standard process encouraged by the 
regulations implementing the National Environmental Policy Act of 1969 
(NEPA) that entails the use of impact analyses of previous EAs to bound 
the impacts of a proposed action where appropriate. The Holtec HI-STORM 
FW MPC Storage System is designed to mitigate the effects of design 
basis accidents that could occur during storage. Considering the 
specific design requirements for the accident conditions, the design of 
the cask would prevent loss of containment, shielding, and criticality 
control. If there is no loss of containment, shielding, or criticality 
control, the environmental impacts would not be significant.
    The exemptions requested by CEG at the NMP site as they relate to 
CoC No. 1032, Amendment No. 3, Revision No. 0, for the HI-STORM FW MPC 
Storage System are limited to using the HI-TRAC during loading and 
transport operations for the MPC-89 for the planned loading of six 
canisters starting in May 2025, despite the NMP site-specific analysis 
of tornado-generated missiles not being performed consistent with the 
NRC-approved method of evaluation in the CoC FSAR, and so the terms, 
conditions, and specifications of the CoC not being met. The staff has 
determined that this change in analysis will not result in either 
radiological or non-radiological environmental impacts that 
significantly differ from the environmental impacts evaluated in the EA 
supporting the issuance of CoC No. 1032, Amendment No. 3, Revision No. 
0. If the exemption is granted, there will be no significant change in 
the types or amounts of any effluents released, no significant increase 
in individual or cumulative public or occupational radiation exposure, 
and no significant increase in the potential for or consequences from 
radiological accidents. Accordingly, the Commission concludes that 
there would be no significant environmental impacts associated with the 
proposed action.

Alternative to the Proposed Action

    The staff considered the no-action alternative. The no-action 
alternative (denial of the exemption request) would require CEG to 
delay the near-term planned loading of spent fuel in the MPC-89 in the 
HI-STORM FW MPC Storage System at the NMP ISFSI. Delaying the loading 
of spent fuel in the six casks in May 2025 could affect CEG's ability 
to effectively manage spent fuel pool capacity, reactor fuel 
offloading, and refueling. Not allowing the planned future loading 
campaign could also pose challenges to spent fuel heat removal and 
impact the availability of the specialized workforce and equipment 
needed to support competing fuel loading and operational activities at 
NMP and other CEG sites.
    The NRC determined that the no-action alternative would result in 
undue potential human health and safety impacts that could be avoided 
by proceeding with the proposed exemption.

Agencies Consulted

    The NRC provided the New York State Energy, Research & Development 
Authority (NYSERDA) a copy of this draft EA for review by an email 
dated February 24, 2025. On February 28, 2025, NYSERDA provided its 
concurrence by email.

III. Finding of No Significant Impact

    The environmental impacts of the proposed action have been reviewed 
in accordance with the requirements in 10 CFR part 51, which implement 
NEPA. Based upon the foregoing EA, the NRC finds that the proposed 
action of granting the exemption from the regulations in 10 CFR 
72.212(a)(2), 72.212(b)(3), 72.212(b)(5)(i), 72.212(b)(11) and 72.214, 
which require the licensee to comply with the terms, conditions, and 
specifications of the CoC, in this case limited to the use of the 
Holtec HI-STORM FW MPC Storage System, including the use of the HI-TRAC 
during loading and transport operations, for the specific near-term 
future loading of six MPC-89 beginning in May 2025, would not 
significantly impact the quality of the human environment. Accordingly, 
the NRC has determined that a FONSI is appropriate,

[[Page 11630]]

and an environmental impact statement is not warranted.

IV. Availability of Documents

    The documents identified in the following table are available to 
interested persons through ADAMS, as indicated.

------------------------------------------------------------------------
                                                ADAMS accession No. or
            Document description               Federal Register notice
------------------------------------------------------------------------
CEG's request for exemption, dated January   ML25022A240.
 22, 2025.
CEG's request for exemption, supplemented,   ML25036A335.
 dated February 4, 2025.
Certificate of Compliance No. 1032,          ML17214A039 (Package).
 Amendment No. 3, Revision No. 0, dated
 August 9, 2017.
Final Safety Analysis Report on the HI-      ML19177A171.
 STORM FW MPC Storage System, Revision No.
 6, dated June 18, 2019.
10 CFR part 72 amendment to allow spent      55 FR 29181.
 fuel storage in NRC-approved casks,
 published July 18, 1990.
EA for part 72 amendment to allow spent      ML051230231.
 fuel storage in NRC-approved casks, dated
 March 8, 1989.
Final rule for List of Approved Spent Fuel   82 FR 29225.
 Storage Casks: Holtec International HI-
 STORM Flood/Wind Multipurpose Canister
 Storage System, Certificate of Compliance
 No. 1032, Amendment No. 3, published June
 28, 2017.
NRC email to NYSERDA, ``Request for State    ML25059A175.
 comments regarding two environmental
 assessments--Nine Mile Point Units 1 and
 2,'' dated February 24, 2025.
NYSERDA email to NRC, ``Response: Request    ML25059A179.
 for State comments regarding two
 environmental assessments--Nine Mile Point
 Units 1 and 2,'' dated February 28, 2025.
------------------------------------------------------------------------


    Dated: March 4, 2025.

    For the Nuclear Regulatory Commission.
Thomas Boyce,
Acting Chief, Storage and Transportation Licensing Branch, Division of 
Fuel Management, Office of Nuclear Material Safety and Safeguards.
[FR Doc. 2025-03762 Filed 3-7-25; 8:45 am]