[Federal Register Volume 85, Number 26 (Friday, February 7, 2020)]
[Notices]
[Pages 7337-7338]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 2020-02437]
[[Page 7337]]
-----------------------------------------------------------------------
NUCLEAR REGULATORY COMMISSION
[Docket Nos. 52-025 and 52-026; NRC-2008-0252]
Southern Nuclear Operating Company, Inc.; Vogtle Electric
Generating Plant, Units 3 and 4; Update to Tier 1 Figure for Steam
Generator System and Main Steam System
AGENCY: Nuclear Regulatory Commission.
ACTION: Exemption and combined license amendment; issuance.
-----------------------------------------------------------------------
SUMMARY: The U.S. Nuclear Regulatory Commission (NRC) is granting an
exemption to allow a departure from the certification information of
Tier 1 of the generic design control document (DCD) and is issuing
License Amendment Nos. 164 and 162 to Combined Licenses (COLs), NPF-91
and NPF-92, respectively. The COLs were issued to Southern Nuclear
Operating Company, Inc., and Georgia Power Company, Oglethorpe Power
Corporation, MEAG Power SPVM, LLC, MEAG Power SPVJ, LLC, MEAG Power
SPVP, LLC, and the City of Dalton, Georgia (collectively SNC); for
construction and operation of the Vogtle Electric Generating Plant
(VEGP) Units 3 and 4, located in Burke County, Georgia.
The granting of the exemption allows the changes to Tier 1
information asked for in the amendment. Because the acceptability of
the exemption was determined in part by the acceptability of the
amendment, the exemption and amendment are being issued concurrently.
DATES: The exemption and amendment were issued on September 27, 2019.
ADDRESSES: Please refer to Docket ID NRC-2008-0252 when contacting the
NRC about the availability of information regarding this document. You
may obtain publicly-available information related to this document
using any of the following methods:
Federal Rulemaking Website: Go to http://www.regulations.gov and search for Docket ID NRC-2008-0252. Address
questions about NRC docket IDs in Regulations.gov to Jennifer Borges;
telephone: 301-287-9127; email: [email protected]. For technical
questions, contact the individual listed in the FOR FURTHER INFORMATION
CONTACT section of this document.
NRC's Agencywide Documents Access and Management System
(ADAMS): You may obtain publicly-available documents online in the
ADAMS Public Documents collection at http://www.nrc.gov/reading-rm/adams.html. To begin the search, select ``Begin Web-based ADAMS
Search.'' For problems with ADAMS, please contact the NRC's Public
Document Room (PDR) reference staff at 1-800-397-4209, 301-415-4737, or
by email to [email protected]. The ADAMS accession number for each
document referenced (if it is available in ADAMS) is provided the first
time that it is mentioned in this document. The request for the
amendment and exemption was designated License Amendment Request (LAR)
19-004 and submitted by letter dated March 29, 2019, and is available
in ADAMS under Accession No. ML19088A126.
NRC's PDR: You may examine and purchase copies of public
documents at the NRC's PDR, Room O1-F21, One White Flint North, 11555
Rockville Pike, Rockville, Maryland 20852.
FOR FURTHER INFORMATION CONTACT: Cayetano Santos, Office of Nuclear
Reactor Regulation, U.S. Nuclear Regulatory Commission, Washington, DC
20555-0001; telephone: 301-415-7270; email: [email protected].
SUPPLEMENTARY INFORMATION:
I. Introduction
The NRC is issuing License Amendment Nos. 164 and 162 to COLs NPF-
91 and NPF-92, respectively, and is granting an exemption from Tier 1
information in the plant-specific DCD for the AP1000. The AP1000 DCD is
incorporated by reference in appendix D, ``Design Certification Rule
for the AP1000,'' to part 52 of title 10 of the Code of Federal
Regulations (10 CFR). The exemption, granted pursuant to paragraph A.4
of section VIII, ``Processes for Changes and Departures,'' of 10 CFR
part 52, appendix D, allows the licensee to depart from the Tier 1
information. With the requested amendment, SNC sought to change COL
Appendix C Figure 2.2.4-1 (Sheet 3) to relocate the auxiliary steam
header isolation valve from the same header as the turbine bypass
valves to a new header.
Part of the justification for granting the exemption was provided
by the review of the amendment. Because the exemption is necessary in
order to issue the requested license amendment, the NRC granted the
exemption and issued the amendment concurrently, rather than in
sequence. This included issuing a combined safety evaluation containing
the NRC staff's review of both the exemption request and the license
amendment. The exemption met all applicable regulatory criteria set
forth in Sec. Sec. 50.12, 52.7, and section VIII.A.4 of appendix D to
10 CFR part 52. The license amendment was found to be acceptable as
well. The combined safety evaluation is available in ADAMS under
Accession No. ML19238A352.
Identical exemption documents (except for referenced unit numbers
and license numbers) were issued to SNC for VEGP Units 3 and 4 (COLs
NPF-91 and NPF-92). The exemption documents for VEGP Units 3 and 4 can
be found in ADAMS under Accession Nos. ML19238A351 and ML19239A089,
respectively. The exemption is reproduced (with the exception of
abbreviated titles and additional citations) in Section II of this
document. The amendment documents for COLs NPF-91 and NPF-92 are
available in ADAMS under Accession Nos. ML19238A346 and ML19238A347,
respectively. A summary of the amendment documents is provided in
Section III of this document.
II. Exemption
Reproduced below is the exemption document issued to VEGP Units 3
and Unit 4. It makes reference to the combined safety evaluation that
provides the reasoning for the findings made by the NRC (and listed
under Item 1) in order to grant the exemption:
1. In a letter dated March 29, 2019, Southern Nuclear Operating
Company requested from the Nuclear Regulatory Commission an exemption
to allow departures from Tier 1 information in the certified Design
Control Document (DCD) incorporated by reference in 10 CFR part 52,
appendix D, ``Design Certification Rule for the AP1000 Design,'' as
part of license amendment request (LAR) 19-004, ``Update to Tier 1
Figure for Steam Generator System and Main Steam System.''
For the reasons set forth in Section 3.1 of the NRC staff's Safety
Evaluation, which can be found at ADAMS Accession Number ML19238A352,
the Commission finds that, the Commission finds that:
A. The exemption is authorized by law;
B. the exemption presents no undue risk to public health and
safety;
C. the exemption is consistent with the common defense and
security;
D. special circumstances are present in that the application of the
rule in this circumstance is not necessary to serve the underlying
purpose of the rule;
E. the special circumstances outweigh any decrease in safety that
may result from the reduction in standardization caused by the
exemption; and
F. the exemption will not result in a significant decrease in the
level of safety otherwise provided by the design.
[[Page 7338]]
2. Accordingly, SNC is granted an exemption from the certified DCD
Tier 1 information, with corresponding changes to Appendix C of the
facility Combined License, as described in the licensee's request dated
March 29, 2019. This exemption is related to, and necessary for, the
granting of License Amendment No. 164 [for unit 3, 162 for Unit 4],
which is being issued concurrently with this exemption.
3. As explained in Section 5.0 of the NRC staff's Safety Evaluation
(ADAMS Accession Number ML19238A352), this exemption meets the
eligibility criteria for categorical exclusion set forth in 10 CFR
51.22(c)(9). Therefore, pursuant to 10 CFR 51.22(b), no environmental
impact statement or environmental assessment needs to be prepared in
connection with the issuance of the exemption.
4. This exemption is effective as of the date of its issuance.
III. License Amendment Request
By letter dated March 29, 2019 (ADAMS Accession No. ML19088A126),
SNC requested that the NRC amend the COLs for VEGP, Units 3 and 4, COLs
NPF-91 and NPF-92. The proposed amendment is described in Section I of
this notice.
The Commission has determined for these amendments that the
application complies with the standards and requirements of the Atomic
Energy Act of 1954, as amended (the Act), and the Commission's rules
and regulations. The Commission has made appropriate findings as
required by the Act and the Commission's rules and regulations in 10
CFR Chapter I, which are set forth in the license amendment.
A notice of consideration of issuance of amendment to facility
operating license or COL, as applicable, proposed no significant
hazards consideration determination, and opportunity for a hearing in
connection with these actions, was published in the Federal Register on
June 4, 2019 (84 FR 25832). No comments were received during the 30-day
comment period.
The Commission has determined that these amendments satisfy the
criteria for categorical exclusion in accordance with 10 CFR 51.22.
Therefore, pursuant to 10 CFR 51.22(b), no environmental impact
statement or environmental assessment need be prepared for these
amendments.
IV. Conclusion
Using the reasons set forth in the combined safety evaluation, the
staff granted the exemptions and issued the amendments that SNC
requested on March 29, 2019.
The exemptions and amendments were issued on September 27, 2019, as
part of a combined package to SNC (ADAMS Accession No. ML19238A345).
Dated at Rockville, Maryland, this 3rd day of February 2020.
For the Nuclear Regulatory Commission.
Victor E. Hall,
Chief, Vogtle Project Office, Office of Nuclear Reactor Regulation.
[FR Doc. 2020-02437 Filed 2-6-20; 8:45 am]
BILLING CODE 7590-01-P