[Federal Register Volume 85, Number 13 (Tuesday, January 21, 2020)] [Rules and Regulations] [Page 3232] From the Federal Register Online via the Government Publishing Office [www.gpo.gov] [FR Doc No: C1-2019-26354] ----------------------------------------------------------------------- DEPARTMENT OF ENERGY 10 CFR Part 430 [Docket Number EERE-2016-BT-STD-0022] RIN 1904-AD69 Energy Conservation Program: Energy Conservation Standards for Uninterruptible Power Supplies Correction In rule document 2019-2635 beginning on page 1447 in the issue of Friday, January 10, 2020, make the following correction: Sec. 430.32 [Corrected] On page 1503, in Sec. 430.32(z)(3) the table should appear as follows: ---------------------------------------------------------------------------------------------------------------- Battery charger product class Rated output power Minimum efficiency ---------------------------------------------------------------------------------------------------------------- 10a (VFD UPSs).......................... 0 W < P <= 300 W................ -1.20E-06 * P 2 + 7.17E-04 * P + 0.862. 300 W < P <= 700 W.............. -7.85E-08 * P 2 + 1.01E-04 * P + 0.946. P > 700 W....................... -7.23E-09 * P 2 + 7.52E-06 * P + 0.977. 10b (VI UPSs)........................... 0 W < P <= 300 W................ -1.20E-06 * P 2 + 7.19E-04 * P + 0.863. 300 W < P <= 700 W.............. -7.67E-08 * P 2 + 1.05E-04 * P + 0.947. P > 700 W....................... -4.62E-09 * P 2 + 8.54E-06 * P + 0.979. 10c (VFI UPSs).......................... 0 W < P <= 300 W................ -3.13E-06 * P 2 + 1.96E-03 * P + 0.543. 300 W < P <= 700 W.............. -2.60E-07 * P 2 + 3.65E-04 * P + 0.764. P > 700 W....................... -1.70E-08 * P 2 + 3.85E-05 * P + 0.876. ---------------------------------------------------------------------------------------------------------------- [FR Doc. C1-2019-26354 Filed 1-17-20; 8:45 am] BILLING CODE 1301-00-D