DEPARTMENT OF HOMELAND SECURITY
Coast Guard
[USCG-2013-0316]
Outer Continental Shelf Units--Fire and Explosion Analyses
AGENCY: Coast Guard, DHS.
ACTION: Notice of recommended interim voluntary guidelines.
-----------------------------------------------------------------------
SUMMARY: As part of its continuing response to the explosion, fire and
sinking of the mobile offshore drilling unit (MODU) DEEPWATER HORIZON
in the Gulf of Mexico on April 20, 2010, the Coast Guard is providing
recommended interim voluntary guidelines concerning fire and explosion
analyses for MODUs and manned fixed and floating offshore facilities
engaged in activities on the U.S. Outer Continental Shelf (OCS).
DATES: The recommended voluntary guidelines in this notice are
effective May 2, 2014.
Documents mentioned as being available in the docket are part of
docket USCG-2013-0316 and are available for inspection or copying at
the Docket Management Facility (M-30), U.S. Department of
Transportation, West Building Ground Floor, Room W12-140, 1200 New
Jersey Avenue SE., Washington, DC 20590, between 9 a.m. and 5 p.m.,
Monday through Friday, except Federal holidays. You may also find this
docket on the Internet by going to http://www.regulations.gov,
inserting USCG-2013-0316 in the ``Keyword'' box, and then clicking
``Search.''
FOR FURTHER INFORMATION CONTACT: If you have questions on this notice,
call or email LCDR John H. Miller, U.S. Coast Guard, Office of Design
and Engineering Standards, Lifesaving and Fire Safety Division (CG-ENG-
4), telephone (202) 372-1372, email [email protected].
Background
The ``Report of Investigation into the Circumstances Surrounding
the Explosion, Fire, Sinking and Loss of Eleven Crew Members Aboard the
Mobile Offshore Drilling Unit (MODU) DEEPWATER HORIZON in the Gulf of
Mexico, April 20-22, 2010,'' (hereinafter referred to as ``Report''),
and related Commandant's Final Action Memo, dated September 9, 2011,
contain a number of recommendations for OCS safety improvements that
are presently being evaluated for further regulatory action. (These
documents may be found in the docket for this action, as indicated
under ADDRESSES).
Recommendations 1D, 1E, 2B, 2C, 2E, and 3A in the Report urged the
Coast Guard to evaluate the need for fire and explosion risk analyses
to ensure an adequate level of protection is provided for accommodation
spaces, escape paths, embarkation stations, and structures housing
vital safety equipment from drill floor and production area events. The
Report highlighted the following considerations as areas not
specifically addressed by current regulations:
Minimum values are needed for explosion design loads for
use in calculating the required blast resistance of structures;
Explosion risk analysis of the design and layout of each
facility should be performed to identify high risk situations;
H-60 rated fire boundaries between the drilling area and
adjacent accommodation spaces and spaces housing vital safety equipment
may be necessary dependent on the arrangement of the facility;
Uniform guidelines for performing engineering evaluations
to ensure adequate protection of bulkheads and decks separating
hazardous areas from adjacent structures and escape routes for likely
drill floor fire scenarios are necessary;
Performance-based fire risk analysis should be used to
supplement the prescriptive requirements in the MODU Code; such
analysis should use defined heat flux loads to calculate necessary
levels of protection for structures, equipment, and vital systems that
could be affected by fires on the drill floor;
Maximum allowable radiant heat exposure limits for
personnel at the muster stations and lifesaving appliance launching
stations in anticipated evacuation scenarios should be implemented.
To implement these recommendations, a future Coast Guard rulemaking
will address fire and explosion risk analyses for MODUs and manned
fixed and floating offshore facilities engaged in OCS activities.
Comments will be invited in connection with that rulemaking.
Currently, there is no requirement in the current OCS regulations,
in Title 33 of the Code of Federal Regulations (CFR), that requires a
fire and explosion analysis that would implement the recommendations
from the Report. Furthermore, while Section 9 of the 2009 IMO MODU Code
contains some recommendations on the parameters of fire and explosion
risk analysis, we believe that these recommendations are not
sufficiently specific to adequately and consistently address these
recommendations from the Report on their own.
We believe that the recommendations from the 2009 IMO MODU Code are
insufficiently specific for several reasons. Section 9.3.1 of the 2009
MODU Code provides, ``In general, accommodation spaces, service spaces
and control stations should not be located adjacent to hazardous areas.
However, where this is not practicable, an engineering evaluation
should be performed to ensure that the level of fire protection and
blast resistance of the bulkheads and decks separating these spaces
from the hazardous areas are adequate for the likely hazard.'' This
requirement is not specific enough to consistently ensure the
protection of safety-critical spaces and elements aboard MODUs and
manned fixed and floating offshore facilities engaged in OCS
activities, and needs to be supported by guidance to better define what
the ``engineering evaluation'' should include and what performance
criteria should be met to ensure ``adequate protection'' is provided.
Safety-critical spaces and elements refers to any accommodation or work
area, equipment, system, device, or material, the failure, destruction,
or release of which could directly or indirectly endanger the
survivability of the facility and the personnel onboard. These safety-
critical spaces and
[[Page 25140]]
elements can include, but not be limited to, control stations,
accommodation areas, vital safety equipment, escape routes and survival
craft launching areas, and other equipment with escalation potential
(e.g., fuel storage). Survivability refers to the event threshold
determined by the company for the purposes of fire and explosion. This
normally includes the specification of a sufficient period of time to
maintain the habitability of safety-critical spaces and escape routes,
temporary refuge, and muster areas to allow for emergency response and
boarding of survival craft and subsequent evacuation of the facility.
Additionally, Section 9.4.5 of the 2009 MODU Code also requires
that, ``Consideration should be given by the Administration to the
siting of superstructures and deckhouses such that in the event of fire
at the drill floor at least one escape route to the embarkation
position and survival craft is protected against radiation effects of
that fire as far as practicable.'' This requirement is not specific
enough to consistently ensure the protection of escape routes aboard
MODUs and manned fixed and floating offshore facilities engaged in OCS
activities, and needs to be supported by guidance to better define what
level of ``radiation effects'' to personnel and safety equipment is
acceptable.
The Coast Guard believes the fire and explosion analysis guidelines
set forth below are needed to uniformly implement the recommendations
in paragraphs 9.3.1 and 9.4.5 of 2009 MODU Code, and address
recommendations 1D, 1E, 2B, 2C, 2E, and 3A of the Report. It is the
Coast Guard's belief that following these recommendations would yield
significant safety improvements. These guidelines were developed based
on industry standards, technical expert advice, and fire protection
engineering references. These guidelines are intended for use in the
design phase of new facility construction; however, they may be useful
in assessing and increasing the safety of existing facilities.
Interim Voluntary Guidance
(a) Introduction
As an interim measure pending a Coast Guard future rulemaking,
owners/operators of MODUs and manned fixed and floating offshore
facilities operating on the U.S. OCS are urged to consider voluntary
compliance with the guidelines laid out below, to the extent
appropriate and practicable.
The intent of the recommendations set forth below is to provide a
consistent approach for adequate protection of personnel and safety-
critical spaces and elements located on MODUS and manned fixed and
floating offshore facilities against potential fire and explosion
events following a catastrophic failure such as loss of well control.
This approach should consider all facility operating modes including
startup, maintenance periods, crew turnover, etc.
(b) Recommendations
(1) Engineering Evaluation
The engineering evaluation of fire and blast loads in the design of
offshore facilities should follow an established and widely accepted
approach, normally based on the fire and explosion risk of hydrocarbon
fuel sources. An engineering evaluation should identify hazards and the
potential damage of major accident events. This evaluation should
consist of a methodology that may include the following: hazard
identification, consequence evaluation, adequacy of control and
mitigation measures, and final risk assessment. The evaluation should
be completed by a Registered Professional Fire Protection Engineer with
experience in fire and explosion analysis, or by a recognized class
society (under 46 CFR part 8) with similar equivalent experience.
This evaluation should include establishment of accepted
performance criteria to demonstrate that appropriate mitigating
measures have been implemented to ensure survivability of the facility
and personnel.
The Coast Guard recommends the use of American Petroleum Institute
(API) Recommended Practice (RP) 2FB for conducting an engineering
evaluation.
We note that there are other standards available that can be used
for the engineering evaluation. We chose API RP 2FB because it contains
thorough coverage of the elements which are important to an engineering
evaluation and because the Coast Guard actively participates in the API
committee process. We do note that there are alternative approaches
that have been widely accepted by the oil and gas industry meeting the
intent of this recommendation.
(2) Explosion Protection
Maximum allowable values for explosion design loads should be
determined based on accepted industry standards and used to calculate
the required blast resistance of structures for each particular
arrangement. Explosion design load means a nominal, peak overpressure
that has been defined in industry standards based on a limited data set
for a number of platform concept types (nominal values are determined
from acquired experience or physical conditions). In cases where
vulnerabilities are noted, facility arrangements should be modified or
additional protective measures provided.
We recommend use of the unmodified nominal explosion overpressures
by facility type and load modifiers listed in API RP 2FB, Tables
C.6.3.1-1 and C.6.3.2-1, where appropriate. As described in the guide,
load modifiers should be used to account for the higher or lower
pressures that may be associated with specific facility arrangements or
operations.
We do note that there are alternative explosion design loads that
have been widely accepted by the oil and gas industry meeting the
intent of this recommendation.
(3) Fire Protection
The radiant heat flux produced by particular hazards should be
prescribed and calculations completed to assess the effects on safety
critical spaces and elements. Radiant heat flux means the rate of heat
transfer per unit area perpendicular to the direction of heat flow;
normally expressed in kilowatts per meters squared (kW/m\2\) or British
Thermal Units per second foot squared (Btu/(s*ft\2\)). Radiant heat
flux is a measure of the potential for injury, damage or fire spread
(e.g., most common combustibles ignite when exposed to a radiant heat
flux of 0.9-1.8 Btu/(s*ft\2\) or 10-20 kW/m\2\).
The radiant heat flux from typical drill floor fire sources should
be approximated from the following:
(i) As specified in API RP 2FB, jet fires may give rise to radiant
heat flux levels on the order of 300 KW/m\2\ in open conditions and up
to 400 KW/m\2\ in confined areas. Jet fire refers to a high-pressure
release of any flammable fluid or gases in a solution that forms a jet
which is ignited, and in which the flame burns back against the flow
towards the release point;
(ii) As specified in API RP 2FB, pool fires may give rise to lower
radiant heat flux levels on the order of 100-160 KW/m\2\. Pool fire
refers to a body of fuel that is confined by physical boundaries (e.g.,
obstructions on the floor will limit a fuel release to a smaller area
than the potential unconfined spill area).
Where the safety-critical spaces and elements are exposed to a
radiant heat flux up to 100 KW/m\2\, a passive structural fire
protection equivalent
[[Page 25141]]
rating of A-60 should generally be considered sufficient for the
surface facing the source of the radiant heat flux. For radiant heat
flux levels 100 KW/m\2\ and above, H-60 rated protection should be
considered as a minimum. In either case, the protection should continue
on the adjacent sides of such structures for a minimum distance of 10
feet (3 meters) from the surface facing the source of the radiant heat
flux (SOLAS II-2/9.2.4.2.5). This overlapping of protection on adjacent
areas is necessary to prevent the radiant heat from ``wrapping around''
to expose an inadequately protected area.
The Coast Guard recommends use of the following references for
calculating the radiant heat flux at a target from a fire source (i.e.,
pool or jet fire).
(i) The SFPE Handbook of Fire Protection Engineering, Fourth
Edition (Section 3, Chapter 10);
(iii) API Recommended Practice 2FB.
We do note that there are alternative baseline radiant heat flux
levels and calculations that have been recognized by the oil and gas
industry meeting the intent of this recommendation.
(4) Heat Exposure
The maximum radiant heat exposure to personnel should be evaluated
at the assembly/muster stations and survival craft launching stations
as well as along the normal escape routes from the accommodation and
service areas to those areas.
The maximum allowable radiant heat flux exposure for personnel at
the muster stations and survival craft launching stations should be low
enough to prevent injury when exposed for the period of time needed to
embark and launch the survival craft (normally around 2.5 KW/m\2\ for
approximately thirty minutes on bare skin).
The Coast Guard recommends use of the following references for
calculating the radiant heat flux exposure to a target and the limits
on personnel exposure:
(i) The SFPE Handbook of Fire Protection Engineering, Fourth
Edition (Section 2, Chapter 6; Section 3, Chapter 10);
(ii) Fire Protection Handbook, Twentieth Edition (Section 6,
Chapter 2);
(iii) API Recommended Practice 2FB.
We do note that there are alternative methods for calculating
radiant heat flux exposure to personnel and exposure limits which meet
the intent of this recommendation.
(5) Mitigation
Where the explosion design load, radiant heat flux and radiant heat
exposure values calculated for the facility exceed the recommended
performance standard of the equipment in place, mitigation measures,
such as venting, increased structural strength of blast-walls,
bulkheads and decks, passive fire protection, re-arrangement and
shifting of structures, or other viable and analyzed mitigation
measures should be incorporated.
Authority; Disclaimer
This document is issued under the authority of 5 U.S.C. 552(a), 43
U.S.C. 1331, et seq., and 33 CFR 1.05-1. The guidance contained in this
notice is not a substitute for applicable legal requirements or current
Coast Guard and Bureau of Safety and Environmental Enforcement
regulations, nor is it itself a regulation. It is not intended to nor
does it impose legally binding requirements on any party. It represents
the Coast Guard's current thinking on this topic and may assist
industry, mariners, the general public, and the Coast Guard, as well as
other Federal and State regulators, in instituting lessons learned from
the Report.