33 U.S.C. 1903(b); 46 U.S.C. 2103, 3306, 4102, 4302; Department of Homeland Security Delegation No. 0170.1(II)(77), (92)(a), 92(b).
The provisions of this part shall apply to all vessels except as specifically noted.
33 CFR parts 175, 177, 179, 181 and 183 contain additional regulations applicable to Uninspected Passenger Vessels.
(a) Certain material is incorporated by reference into this subchapter with the approval of the Director of the Federal Register in accordance with 5 U.S.C. 552(a) and 1 CFR part 51. All approved material is available for inspection at the U.S. Coast Guard, Office of Design and Engineering Standards (CG-ENG-4), 2703 Martin Luther King Jr. Avenue SE., Stop 7509, Washington, DC 20593-7509, and is available from the
(b) American Boat and Yacht Council (ABYC), 613 Third Street, Suite 10, Annapolis, MD 21403, 410-990-4460,
(1) Standard A-1-78, Marine LPG-Liquefied Petroleum Gas Systems, December 15, 1978, IBR approved for § 25.45-2(b).
(2) Standard A-22-78, Marine CNG-Compressed Natural Gas Systems, December 15, 1978, IBR approved for § 25.45-2(b).
(3) Standard A-16-97, Electric Navigation Lights, July 1997, IBR approved for § 25.10-3(a).
(c) National Fire Protection Association (NFPA), 1 Batterymarch Park, Quincy, MA 02169, 617-770-3000,
(1) NFPA 10, Standard for Portable Fire Extinguishers, 2010 Edition, effective December 5, 2009, IBR approved for § 25.30-10(a) through (d).
(2) NFPA 13, Standard for the Installation of Sprinkler Systems, 2010 Edition, effective August 26, 2009, IBR approved for § 25.30-15(c).
(3) NFPA 302, Fire Protection Standard for Pleasure and Commercial Motor Craft, 1989, IBR approved for § 25.45-2(b).
(d) Society of Automotive Engineers (SAE), 400 Commonwealth Drive, Warrendale, PA 15096, 724-776-4841,
(1) SAE J-1928, Devices Providing Backfire Flame Control for Gasoline Engines in Marine Applications, June 1, 1989, IBR approved for § 25.35-1.
(2) [Reserved]
(e) UL (formerly Underwriters Laboratories), 12 Laboratory Drive, Research Triangle Park, NC 27709, 919-549-1400,
(1) UL 1111, Marine Carburetor Flame Arrestors, June 1988, IBR approved for § 25.35-1.
(2) [Reserved]
(a)
(b)
This subpart applies to vessel manufacturers, distributors, and dealers installing navigation lights on all uninspected commercial vessels, except those completed before November 7, 2002.
As used in this subpart:
(1) The manufacture, construction, or assembly of vessels, or
(2) The importation of vessels into the United States for subsequent sale.
(a) Except as provided by paragraph (b) of this section, each navigation light must—
(1) Meet the technical standards of the applicable Navigation Rules;
(2) Be certified by a laboratory listed by the Coast Guard to the standards of ABYC A-16 (incorporated by reference, see § 25.01-3), or equivalent, although portable battery-powered lights need only meet the requirements of the standard applicable to them; and
(3) Bear a permanent and indelible label stating the following:
(i) “USCG Approval 33 CFR 183.810”
(ii) “MEETS __.” (Insert the identification name or number of the standard under paragraph (a)(2) of this section, to which the light was type-tested.)
(iii) “TESTED BY __.” (Insert the name or registered certification-mark of the laboratory listed by the Coast Guard that tested the fixture to the standard under paragraph (a)(2) of this section.)
(iv) Name of Manufacturer.
(v) Number of Model.
(vi) Visibility of the light in nautical miles (nm).
(vii) Date on which the light was type-tested.
(viii) Identification of bulb used in the compliance test.
(b) If a light is too small to attach the required label—
(1) Place the information from the label in or on the package that contains the light; and
(2) Mark each light “USCG” followed by the certified range of visibility in nautical miles, for example, “USCG 2nm.” Once installed, this mark must be visible without removing the light.
This subpart applies to each vessel to which this part applies, except:
(a) Vessels used for noncommercial use; and
(b) Vessels leased, rented, or chartered to another for the latter's noncommercial use.
As used in this subpart:
(a)
(b)
(c)
(a) No person may operate a vessel to which this subpart applies unless it meets the requirements of this subpart.
(b) (1) Each vessel not carrying passengers for hire and less than 40 feet in length must have on board at least one wearable personal flotation device (PFD) approved under subchapter Q of this chapter, and of a suitable size for each person on board.
(2) Each vessel carrying passengers for hire, and each vessel not carrying passengers for hire and 40 feet in length or longer, must have at least one PFD approved under approval series 160.055, 160.155, or 160.176, and of a suitable size for each person on board.
(3) In addition to the equipment required by paragraphs (b)(1) and (b)(2) of this section, each vessel 26 feet in length or longer, except for a barge to which this subpart applies, must have at least one approved lifebuoy, and each uninspected passenger vessel of at
(c)(1) Each vessel not carrying passengers for hire may substitute an immersion suit approved under 46 CFR 160.171 for a wearable PFD required under paragraphs (b)(1) or (b)(2) of this section.
(2) On each vessel, regardless of length and regardless of whether carrying passengers for hire, an approved commercial hybrid PFD approved under approval series 160.077, may be substituted for a PFD approved under approval series 160.055, 160.155, or 160.176, if it is—
(i) Used in accordance with the conditions marked on the PFD and in the owner's manual; and
(ii) Labeled for use on commercial vessels.
The lifesaving equipment required by this subpart must be legibly marked as specified in subchapter Q of this chapter.
(a) The lifesaving equipment designed to be worn required in § 25.25-5(b) and (c) must be readily accessible.
(b) Lifesaving equipment designed to be thrown required in § 25.25-5(b) must be immediately available.
(c) For a barge to which this subpart applies, the wearable lifesaving equipment specified in § 25.25-5 need not be stored on board the barge if the barge's operator stores it elsewhere, and ensures that each individual dons the equipment or a work vest approved under 46 CFR 160.053 before boarding the barge and keeps it on for as long as the individual remains on board and at risk of falling overboard.
The lifesaving equipment required by this subpart must be in serviceable condition.
(a) This section applies to vessels described in § 25.25-1 that engage in ocean, coastwise, or Great Lakes voyages.
(b) Each immersion suit carried in accordance with § 25.25-5(e), each life preserver, each marine buoyant device intended to be worn, and each buoyant vest must have a personal flotation device light that is approved under subpart 161.012 of this chapter.
(c) Each personal flotation device light required by this section must be securely attached to the front shoulder area of the immersion suit, life preserver, or other personal flotation device.
(d) If a personal flotation device light has a non-replaceable power source, the light must be replaced on or before the expiration date of the power source. If the light has a replaceable power source, the power source must be replaced on or before its expiration date and the light must be replaced when it is no longer serviceable.
(a) Each life preserver, each marine buoyant device intended to be worn, and each buoyant vest carried on a vessel must have Type I retroreflective material that is approved under subpart 164.018 of this chapter.
(b) Each item required to have retroreflective material must have at least 200 sq. cm (31 sq. in.) of material attached to its front side, at least 200 sq. cm of material on its back side, and, if the item is reversible, at least 200 sq. cm of material on each of its reversible sides. The material attached on each side of the item must be divided equally between the upper quadrants of the side, and the material in each quadrant must be attached as
(a) Each uninspected passenger vessel of at least 100 gross tons must have adequate survival craft with enough capacity for all persons aboard and must meet one of the following requirements:
(1) An inflatable liferaft must be approved under 46 CFR part 160, subparts 160.051 or 160.151, and be equipped with an applicable equipment pack or be approved by another standard specified by the Commandant. Inflatable liferafts must be serviced at a servicing facility approved under 46 CFR part 160, subpart 160.151.
(2) An inflatable buoyant apparatus must be approved under 46 CFR part 160, subpart 160.010 or under another standard specified by the Commandant. An inflatable buoyant apparatus must be serviced at a servicing facility approved under 46 CFR part 160, subpart 160.151.
(b) If the vessel carries a small boat or boats, the capacity of the small boat or boat(s) may be counted toward the survival craft capacity required by this part. Such small boat or boat(s) must meet the requirements for safe loading and floatation in 33 CFR part 183.
Each uninspected passenger vessel must meet the visual distress signal requirements of 33 CFR part 175 applicable to the vessel.
As used in this subpart:
As an example, a vessel on a voyage involving catching fish which are to be sold, is a commercial fishing industry vessel for the purposes of the EPIRB regulations in this section, even if there are passengers on board during the voyage.
(a) The owner of a fishing vessel, a fish processing vessel, or a fish tender vessel, 11 meters (36 feet) or more in length, except for vessels described in paragraph (b) or (c) of this section, shall ensure that the vessel does not operate on the high seas or beyond three miles from the coastline of the Great Lakes unless it has on board a float-free, automatically activated Category 1 406 MHz EPIRB stowed in a manner so that it will float-free if the vessel sinks.
(b) The owner of a fishing vessel, fish processing vessel, or a fish tender vessel less than 11 meters (36 feet) in length, or 11 meters or more in length which has a builder's certification that the vessel is constructed with sufficient inherently buoyant material to keep the flooded vessel afloat, shall ensure that the vessel does not operate on the high seas or beyond three miles from the coastline of the Great Lakes, unless it has installed in a readily accessible location at or near the principal steering station—
(1) A manually activated Category 2 406 MHz EPIRB; or
(2) A float-free, automatically activated Category 1 406 MHz EPIRB.
(3) Until February 1, 1998, a 121.5/243.0 MHz EPIRB meeting § 25.26-30.
(c) The owner of a fishing vessel, fish processing vessel or a fish tender vessel 11 meters (36 feet) or more in length that does not have installed galley or berthing facilities, shall ensure that the vessel does not operate on the high seas or beyond three miles from the coastline of the Great Lakes unless it has on board a float-free, automatically activated Category 1 406 MHz EPIRB stowed in a manner so that it will float free if the vessel sinks.
(a) Uninspected passenger vessels less than 100 gross tons are not required to carry an EPIRB.
(b) The owner, operator, or master of an uninspected passenger vessel of at least 100 gross tons must ensure that the vessel does not operate beyond three miles from shore as measured from the territorial sea baseline seaward or more than three miles from the coastline of the Great Lakes, unless it has onboard a float-free, automatically activated Category 1 406 MHz EPIRB stowed in a manner so that it will float free if the vessel sinks.
(a) The owner of a manned uninspected commercial vessel 11 meters (36 feet) or more in length, other than a vessel under § 25.26-5 or § 25.26-10 or under paragraph (b) of this section, shall ensure that the vessel does not operate on the high seas or beyond three miles from the coastline of the Great Lakes, unless it has on board a float-free, automatically activated Category 1 406 MHz EPIRB stowed in a manner so that it will float free if the vessel sinks.
(b) The owner of a manned uninspected commercial vessel less than 11 meters (36 feet) in length, or 11 meters or more in length which has a builder's certification that the vessel is constructed with sufficient inherently buoyant material to keep the flooded vessel afloat, shall ensure that the vessel does not operate on the high seas or beyond three miles from the coastline of the Great Lakes, unless it has installed in a readily accessible location at or near the principal steering station—
(1) A manually activated Category 2 406 MHz EPIRB; or
(2) A float-free, automatically activated Category 1 406 MHz EPIRB.
(a) The master of each vessel required to have an EPIRB under this subpart shall ensure that each EPIRB on board is tested and serviced as required by this section.
(b) The EPIRB must be tested immediately after installation and at least once each month thereafter, unless it is an EPIRB installed in a Coast Guard approved inflatable liferaft that is tested annually during the servicing of the liferaft by an approved servicing facility. The test shall be conducted in accordance with the manufacturer's instructions, using the visual or audio indicator on the EPIRB. If the EPIRB is not operating, it must be repaired or replaced with an operating EPIRB.
(c) The battery of the EPIRB must be replaced—
(1) Immediately after the EPIRB is used for any purpose other than being tested; and
(2) Before the expiration date that is marked on the battery.
(a) A skiff or work boat is not required to carry an EPIRB if—
(1) Its “mother ship” is required to carry an EPIRB under this subpart; and
(2) When not in use, the skiff or work boat is carried on board the mother ship.
(b) Each Coast Guard District Commander may, on a case-by-case basis, grant exemptions from the carriage requirements of EPIRBs in this subpart for certain geographic areas within the boundaries of his or her own district if the District Commander determines that an EPIRB will not significantly enhance the overall safety of the vessel and crew. Exemptions may be limited to specific time periods. Exemptions granted under this paragraph must be:
(1) Issued in writing by the cognizant Coast Guard District Commander for each individual application; and
(2) For geographic locations and may be limited to specific time periods.
(a) The provisions of this subpart, with the exception of §§ 25.30-80 and 25.30-90 of this subpart, as applicable, apply to all vessels contracted for on or after August 22, 2016.
(b) Vessels contracted for prior to August 22, 2016 and after November 19, 1952, must meet the requirements of 46 CFR 25.30-80.
(c) Vessels contracted for prior to November 19, 1952, must meet the requirements of 46 CFR 25.30-90.
(a) Where equipment in this subpart is required to be of an approved type, such equipment requires the specific approval of the Commandant. Such approvals are published in the
(b) All hand portable fire extinguishers, semiportable fire extinguishing systems, and fixed fire extinguishing systems shall be of an approved type.
(a) Portable and semi-portable extinguishers must be inspected and maintained in accordance with NFPA 10 (incorporated by reference, see § 25.01-3).
(b) Certification or licensing by a state or local jurisdiction as a fire extinguisher servicing agency will be accepted by the Coast Guard as meeting the personnel certification requirements of NFPA 10 for annual maintenance and recharging of extinguishers.
(c) Monthly inspections required by NFPA 10 may be conducted by the owner, operator, person-in-charge, or a designated member of the crew.
(d) Non-rechargeable or non-refillable extinguishers must be inspected and maintained in accordance with NFPA 10; however, the annual maintenance need not be conducted by a certified person and can be conducted by the owner, operator, person-in-charge, or a designated member of the crew.
(e) The owner or managing operator must provide satisfactory evidence of the required servicing to the marine inspector. If any of the equipment or records has not been properly maintained, a qualified servicing facility must perform the required inspections, maintenance procedures, and hydrostatic pressure tests. A tag issued by a qualified servicing organization, and attached to each extinguisher, may be accepted as evidence that the necessary maintenance procedures have been conducted.
(f) Vaporizing-liquid type fire extinguishers containing carbon tetrachloride, chlorobromomethane, or other toxic vaporizing liquids are not
(g) Portable or semi-portable extinguishers, which are required on their name plates to be protected from freezing, must not be located where freezing temperatures may be expected.
(h) The use of dry chemical, stored pressure, fire extinguishers not fitted with pressure gauges or indicating devices, manufactured prior to January 1, 1965, may be permitted on motorboats and other vessels so long as such extinguishers are maintained in good and serviceable condition. The following maintenance and inspections are required for such extinguishers:
(1) When the date on the inspection record tag on the extinguishers shows that 6 months have elapsed since the last weight check ashore, then such extinguishers are no longer accepted as meeting required maintenance conditions until they are reweighed ashore, found to be in a serviceable condition, and within required weight conditions.
(2) If the weight of the container is
(3) If the outer seal or seals (which indicate tampering or use when broken) are not intact, the boarding officer or marine inspector will inspect such extinguishers to see that the frangible disc in the neck of the container is intact; and if such disc is not intact, the container must be serviced.
(4) If there is evidence of damage, use, or leakage, such as dry chemical powder observed in the nozzle or elsewhere on the extinguisher, the extinguisher must be serviced or replaced.
(i) Dry chemical extinguishers, stored pressure extinguishers, and fire extinguishers without pressure gauges or indicating devices manufactured after January 1, 1965, cannot be labeled with the marine type label described in 46 CFR 162.028-4. These extinguishers manufactured after January 1, 1965, may be carried onboard motorboats or other vessels as excess equipment.
(j) Semi-portable extinguishers must be fitted with a suitable hose and nozzle, or other practicable means, so that all portions of the space concerned may be covered.
(a) When a fixed fire extinguishing system is installed, it must be a type approved or accepted by the Commandant (CG-ENG-4) or the Commanding Officer, U.S. Coast Guard Marine Safety Center.
(b) If the system is a carbon-dioxide type, then it must be designed and installed in accordance with subpart 76.15 of part 76 of subchapter H (Passenger Vessels) of this chapter.
(c) If the system is an automatic sprinkler system then it must be designed and installed in accordance with Chapter 25 of NFPA 13 (incorporated by reference, see § 25.01-3).
(a)
(2) The intent of this regulation is illustrated in Figure 25.30-20(a1) where fire extinguishers are required if any one or more of the specified conditions exist, and in Figure 25.30-20(a2) where specified conditions do not, in themselves, require that fire extinguishers be carried.
Fire extinguishers are required if any one or more of the following conditions exist (numbers identifying conditions are the same as those placed in Figure 25.30-20 (a1)):
1. Closed compartment under thwarts and seats wherein portable fuel tanks may be stored.
2. Double bottoms not sealed to the hull or which are not completely filled with flotation material.
3. Closed living spaces.
4. Closed stowage compartments in which combustible or flammable materials are stowed.
5. Permanently installed fuel tanks.
The following conditions do not, in themselves, require that fire extinguishers be carried (numbers identifying conditions are the same as those placed in Figure 25.30-20(a2)):
1. Bait wells.
2. Glove compartments.
3. Buoyant flotation material.
4. Open slatted flooring.
5. Ice chests.
(3) Table 25.30-20(a)(1) of this section indicates the minimum quantity and type of extinguisher to be carried. Extinguishers with larger numerical ratings or multiple letter designations may be used if the extinguishers meet the requirements of the table.
(b)
(c)
(2) In addition to the portable fire extinguishers required by paragraph (b)(1) of this section, the following fire extinguishing equipment must be fitted in the machinery space:
(i) One Type 20-B portable fire extinguisher must be carried for each 1,000 B. H. P. of the main engines or fraction thereof. However, not more than 6 such extinguishers need be carried.
(ii) On motor vessels of over 300 gross tons, either one 160-B semi-portable fire extinguishing system must be fitted, or alternatively, a fixed fire extinguishing system must be fitted in the machinery space.
(3) The frame or support of each 160-B fire extinguisher required by paragraph (b)(2)(ii) of this section must be welded or otherwise permanently attached to a bulkhead or deck.
(4) If an approved semi-portable fire extinguisher has wheels, it must be securely stowed when not in use to prevent it from rolling out of control under heavy sea conditions.
(5) Table 25.30-20(b)(1) of this section indicates the minimum quantity and type of extinguisher to be carried. Extinguishers with larger numerical ratings or multiple letter designations may be used if the extinguishers meet the requirements of the table.
(d)
(2) Every barge of over 65 feet in length while carrying passengers when towed or pushed by a motorboat, motor vessel, or steam vessel must be fitted
Vessels contracted for prior to August 22, 2016 must meet the following requirements:
(a) Previously installed extinguishers with extinguishing capacities smaller than what is required in tables 25.30-20(a)(1) and 25.30-20(b)(1) of this subpart need not be replaced and may be continued in service so long as they are maintained in good condition to the satisfaction of the Officer in Charge, Marine Inspection.
(b) All new equipment and installations must meet the applicable requirements in this subpart for new vessels.
(a) Vessels contracted for prior to November 19, 1952, shall meet the applicable provisions of §§ 25.30-5 through 25.30-20 insofar as the number and general type of equipment is concerned. Existing items of equipment and installations previously approved but not meeting the applicable requirements for type approval may be continued in service so long as they are in good condition. All new installations and replacements shall meet the requirements of §§ 25.30-5 through 25.30-20.
(b) [Reserved]
(a) Every gasoline engine installed in a motorboat or motor vessel after April 25, 1940, except outboard motors, shall be equipped with an acceptable means of backfire flame control.
(b) Installations made before November 19, 1952, need not meet the detailed requirements of this subpart and may be continued in use as long as they are serviceable and in good condition. Replacements shall meet the applicable conditions in this section.
(c) Installations consisting of backfire flame arresters bearing basic Approval Nos. 162.015 or 162.041 or engine air and fuel induction systems bearing basic Approval Nos. 162.015 or 162.042 may be continued in use as long as they are serviceable and in good condition. New installations or replacements must meet applicable requirements of subpart 58.10 of this chapter.
(a) All motorboats or motor vessels, except open boats and as provided in paragraphs (d) and (e) of this section, the construction or decking over of which is commenced after April 25, 1940, and which use fuel having a flashpoint of 110 °F., or less, shall have at least two ventilator ducts, fitted with cowls or their equivalent, for the efficient removal of explosive or flammable gases from the bilges of every engine and fuel tank compartment. There shall be at least one exhaust duct installed so as to extend from the open atmosphere to the lower portion of the bilge and at least one intake duct installed so as to extend to a point at least midway to the bilge or at least below the level of the carburetor air intake. The cowls shall be located and trimmed for maximum effectiveness and in such a manner so as to prevent displaced fumes from being recirculated.
(b) As used in this section, the term
(c) Boats built after July 31, 1980, which are manufactured or used primarily for noncommercial use; which
(d) Boats built after July 31, 1978, which are manufactured or used primarily for noncommercial use; which are rented, leased, or chartered to another for the latter's noncommercial use; or which engage in conveying six or fewer passengers are exempted from the requirements of paragraph (a) for fuel tank compartments that:
(1) Contain a permanently installed fuel tank if each electrical component is ignition protected in accordance with 33 CFR 183.410(a); and
(2) Contain fuel tanks that vent to the outside of the boat.
(a) No fuel may be used in any heating or lighting system on any vessel carrying passengers for hire without the approval of Commandant (CG-ENG), except—
(1) Alcohol, solid,
(2) Alcohol, liquid, combustible,
(3) Fuel oil, No. 1, No. 2, or No. 3,
(4) Kerosene,
(5) Wood or,
(6) Coal.
(b) Heating and lighting systems using alcohol must meet the following requirements:
(1) Containers of solidified alcohol must be properly secured to a fixed base.
(2) Fluid alcohol burners, where wet priming is used, must have—
(i) A catch pan of not less than
(ii) The metal protection under the stove flanged up at least
(c) Heating and lighting systems using kerosene or fuel oil must meet the following requirements:
(1) Where wet priming is used, each system must have—
(i) A catch pan of not less than
(ii) The metal protection under the stove flanged up at least
(2) Fuel tanks must be—
(i) Separated from the stove that they serve;
(ii) Mounted in a location open to the atmosphere or mounted inside a compartment that is vented to the atmosphere; and
(iii) Fitted with an outside fill and vent.
(d) Heating systems using wood or coal installed after August 9, 1989, shall be installed in accordance with the guidelines in chapter 6 of NFPA 302.
(a) No fuel may be used in any cooking system on any vessel carrying passengers for hire without the approval of Commandant (CG-ENG) except those listed in § 25.45-1, subject to the requirements stated therein, and liquefied petroleum gas (LPG), or compressed natural gas (CNG).
(b) Cooking systems using LPG or CNG must meet the following requirements:
(1) The design, installation, and testing of each LPG system must meet ABYC A-1-78 or chapter 6 of NFPA 302.
(2) The design, installation, and testing of each CNG system must meet ABYC A-22-78 or chapter 6 of NFPA 302.
(3) Cooking systems using chapter 6 of NFPA 302 as the standard must meet the following additional requirements:
(i) The storage or use of CNG containers within the accommodation area, machinery spaces, bilges, or other enclosed spaces is prohibited.
(ii) LPG or CNG must be odorized in accordance with ABYC A-1.5.d or A-22.5.b, respectively.
(iii) The marking and mounting of LPG cylinders must be in accordance with ABYC A-1.6.b.
(iv) LPG cylinders must be of the vapor withdrawal type as specified in ABYC A-1.5.b.
(4) Continuous pilot lights or automatic glow plugs are prohibited for an LPG or CNG installation using ABYC A-1 or A-22 as the standard.
(5) CNG installations using ABYC A-22 as the standard must meet the following additional requirements:
(i) The stowage or use of CNG containers within the accommodation area, machinery spaces, bilges, or other enclosed spaces is prohibited.
(ii) The CNG cylinders, regulating equipment, and safety equipment must meet the installation, stowage, and testing requirements specified in paragraph 6-5.12 of NFPA 302.
(iii) The use of stowage of stoves with attached CNG cylinders is prohibited as specified in paragraph 6-5.1 of NFPA 302.
(6) If the fuel supply line of an LPG or CNG system enters an enclosed space on the vessel, a remote shut-off valve must be installed that can be operated from a position adjacent to the appliance. The valve must be located between the fuel tank and the point where the fuel supply line enters the enclosed portion of the vessel. A power operated valve installed to meet this requirement must be of a type that will fail closed.
(7) The following variances from ABYC A-1.11.b(1) are allowed for CNG:
(i) The storage locker or housing access opening need not be in the top.
(ii) The locker or housing need not be above the waterline.
(8) The following variances from NFPA 302 are allowed:
(i) The storage locker or housing for CNG tank installations need not be above the waterline as required by paragraph 6-5.12.1.1(a).
(ii) Ignition protection need not be provided as required by paragraph 6-5.4.
The ABYC and NFPA standards referenced in this section require the posting of placards containing safety precautions for gas cooking systems.
Each uninspected vessel must meet the garbage discharge, waste management plan, and placard requirements of 33 CFR part 151 applicable to the vessel.
33 CFR 151.67 prohibits the discharge of plastic or garbage mixed with plastic into the sea or the navigable waters of the United States. “Plastic” and “garbage” are defined in 33 CFR 151.05.