    <TITLE>Equipment and conductor grounding.</TITLE>
    <GRANULENUM>183.372</GRANULENUM>
    <HEADING>Section 183.372</HEADING>
    <ANCESTORS>
      <PARENT HEADING="Title 46" SEQ="4">Shipping</PARENT>
      <PARENT HEADING="CHAPTER I" SEQ="3">COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED)</PARENT>
      <PARENT HEADING="SUBCHAPTER T" SEQ="2">SMALL PASSENGER VESSELS (UNDER 100 GROSS TONS)</PARENT>
      <PARENT HEADING="PART 183" SEQ="1">ELECTRICAL INSTALLATION</PARENT>
      <PARENT HEADING="Subpart C" SEQ="0">Power Sources and Distribution Systems</PARENT>
    </ANCESTORS>
  </FDSYS>
  <SECTION>
    <SECTNO>§ 183.372</SECTNO>
    <SUBJECT>Equipment and conductor grounding.</SUBJECT>
    <P>(a) All metallic enclosures and frames of electrical equipment must be permanently grounded to the hull on a metallic vessel. On a nonmetallic vessel, the enclosures and frames of electrical equipment must be bonded together to a common ground by a normally non-current carrying conductor. Metallic cases of instruments and secondary windings of instrument transformers must be grounded.</P>
    <P>(b) On a nonmetallic vessel, where a ground plate is provided for radio equipment, it must be connected to the common ground.</P>
    <P>(c) Equipment grounding conductors must be sized in accordance with Section 250-96 of NFPA 70 (incorporated by reference; see 46 CFR 175.600), or other standard specified by the Commandant.</P>
    <P>(d) Each insulated grounding conductor of a cable must be identified by one of the following means:</P>
    <P>(1) A green braid or green insulation;</P>
    <P>(2) Stripping the insulation from the entire exposed length of the grounding conductor; or</P>
    <P>(3) Marking the exposed insulation of the grounding conductor with green tape or green adhesive labels.</P>
    <P>(e) Cable armor must not be used to ground electrical equipment or systems.</P>
    <CITA>[CGD 85-080, 61 FR 997, Jan. 10, 1996, as amended by USCG-2003-16630, 73 FR 65210, Oct. 31, 2008]</CITA>