    <TITLE>Flammable vapor detection systems.</TITLE>
    <GRANULENUM>182.480</GRANULENUM>
    <HEADING>Section 182.480</HEADING>
    <ANCESTORS>
      <PARENT HEADING="Title 46" SEQ="4">Shipping</PARENT>
      <PARENT HEADING="CHAPTER I" SEQ="3">COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED)</PARENT>
      <PARENT HEADING="SUBCHAPTER T" SEQ="2">SMALL PASSENGER VESSELS (UNDER 100 GROSS TONS)</PARENT>
      <PARENT HEADING="PART 182" SEQ="1">MACHINERY INSTALLATION</PARENT>
      <PARENT HEADING="Subpart D" SEQ="0">Specific Machinery Requirements</PARENT>
    </ANCESTORS>
  </FDSYS>
  <SECTION>
    <SECTNO>§ 182.480</SECTNO>
    <SUBJECT>Flammable vapor detection systems.</SUBJECT>
    <P>(a) A flammable vapor detection system required by § 182.410(c) must meet UL 1110 (incorporated by reference; see 46 CFR 175.600) or be approved by an independent laboratory.</P>
    <P>(b) Procedures for checking the proper operation of a flammable vapor detection system must be posted at the primary operating station. The system must be self-monitoring and include a ground fault indication alarm.</P>
    <P>(c) A flammable vapor detection system must be operational for 30 seconds prior to engine startup and continue sensing the entire time the engine is running.</P>
    <P>(d) A flammable vapor detection system must provide a visual and audible alarm at the operating station.</P>
    <P>(e) A sensor must be located above the expected bilge water level in the following locations:</P>
    <P>(1) The lowest part of a machinery space;</P>
    <P>(2) The lowest part of a space containing a fuel tank when separate from the machinery space; and</P>
    <P>(3) Any other location when required by the cognizant OCMI.</P>
    <P>(f) A flammable vapor detection system must be installed so as to permit calibration in a vapor free atmosphere.</P>
    <P>(g) Electrical connections, wiring, and components for a flammable vapor detection system must comply with part 183 of this chapter.</P>
    <P>(h) An operation and maintenance manual for the flammable vapor detection system must be kept onboard.</P>
    <CITA>[CGD 85-080, 61 FR 986, Jan. 10, 1996, as amended by USCG-2003-16630, 73 FR 65209, Oct. 31, 2008]</CITA>