    <TITLE>Tests for approval.</TITLE>
    <GRANULENUM>162.161-6</GRANULENUM>
    <HEADING>Section 162.161-6</HEADING>
    <ANCESTORS>
      <PARENT HEADING="Title 46" SEQ="4">Shipping</PARENT>
      <PARENT HEADING="CHAPTER I" SEQ="3">COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED)</PARENT>
      <PARENT HEADING="SUBCHAPTER Q" SEQ="2">EQUIPMENT, CONSTRUCTION, AND MATERIALS: SPECIFICATIONS AND APPROVAL</PARENT>
      <PARENT HEADING="PART 162" SEQ="1">ENGINEERING EQUIPMENT</PARENT>
      <PARENT HEADING="Subpart 162.161" SEQ="0">Fixed Clean Agent Fire Extinguishing Systems</PARENT>
    </ANCESTORS>
  </FDSYS>
  <SECTION>
    <SECTNO>§ 162.161-6</SECTNO>
    <SUBJECT>Tests for approval.</SUBJECT>
    <P>Prior to approval by an independent laboratory each system must:</P>
    <P>(a) Satisfy the test method of MSC/Circ. 848 as amended by MSC.1/Circ. 1267 (both incorporated by reference, see § 162.161-2), except that:</P>
    <P>(1) The Fire Type A (Tell tale) test must be conducted when the charged system cylinders have been conditioned for 24 hours at 32 °F or at the expected service temperature, if lower than 32 °F.</P>
    <P>(2) [Reserved]</P>
    <P>(b) Satisfy the following test requirements as indicated in UL 2166 (incorporated by reference, see § 162.161-2) for halocarbon systems or UL 2127 for inert gas systems (incorporated by reference, see § 162.161-2):</P>
    <P>(1) Nozzle distribution;</P>
    <P>(2) Flow calculation method verification to determine that the manufacturer's calculation method accurately predicts the discharge time, nozzle pressure, and distribution of the extinguishing agent;</P>
    <P>(3) Salt spray corrosion resistance for marine-type systems;</P>
    <P>(4) Vibration resistance of installed components for marine-type systems; and</P>

    <P>(5) Any additional tests contained in UL 2166 for halocarbon systems or UL 2127 for inert gas systems, as required for listing by the independent laboratory.<PRTPAGE P="377"/>
    </P>
    <P>(c) Equivalent length of installed components must be identified and included in the test report in accordance with UL 2166 (incorporated by reference, see § 162.161-2) for halocarbon systems or UL 2127 (incorporated by reference, see § 162.161-2) for inert gas systems.</P>
  </SECTION>