<?xml version="1.0"?>
<?xml-stylesheet type="text/xsl" href="cfr.xsl"?>
<CFRGRANULE xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:noNamespaceSchemaLocation="CFRMergedXML.xsd">
  <FDSYS>
    <CFRTITLE>46</CFRTITLE>
    <CFRTITLETEXT>Shipping</CFRTITLETEXT>
    <VOL>2</VOL>
    <DATE>2013-10-01</DATE>
    <ORIGINALDATE>2013-10-01</ORIGINALDATE>
    <COVERONLY>false</COVERONLY>
    <TITLE>Relief valve requirements for hot water boilers (modifies HG-400.2).</TITLE>
    <GRANULENUM>53.05-2</GRANULENUM>
    <HEADING>Section 53.05-2</HEADING>
    <ANCESTORS>
      <PARENT HEADING="Title 46" SEQ="4">Shipping</PARENT>
      <PARENT HEADING="CHAPTER I" SEQ="3">COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED)</PARENT>
      <PARENT HEADING="SUBCHAPTER F" SEQ="2">MARINE ENGINEERING</PARENT>
      <PARENT HEADING="PART 53" SEQ="1">HEATING BOILERS</PARENT>
      <PARENT HEADING="Subpart 53.05" SEQ="0">Pressure Relieving Devices (Article 4)</PARENT>
    </ANCESTORS>
  </FDSYS>
  <SECTION>
    <SECTNO>§ 53.05-2</SECTNO>
    <SUBJECT>Relief valve requirements for hot water boilers (modifies HG-400.2).</SUBJECT>
    <P>(a) The relief valve requirements for hot water boilers must be as indicated in article 4 of section IV of the ASME Boiler and Pressure Vessel Code (incorporated by reference; see 46 CFR 53.01-1) except as noted otherwise in this section.</P>
    <P>(b) <E T="03">Hot water heating boilers.</E> Each hot water heating boiler must have at least one safety relief valve.</P>
    <P>(c) <E T="03">Hot water supply boilers.</E> Each hot water supply boiler must have at least one safety relief valve and a temperature relief valve or a pressure-temperature relief valve. The valve temperature setting must not be more than 99 °C (210 °F).</P>
    <CITA>[CGD 81-79, 50 FR 9435, Mar. 8, 1985, as amended by USCG-2003-16630, 73 FR 65163, Oct. 31, 2008]</CITA>
  </SECTION>