[Title 29 CFR 1910.303]
[Code of Federal Regulations (annual edition) - July 1, 2002 Edition]
[Title 29 - LABOR]
[Subtitle B - Regulations Relating to Labor (Continued)]
[Chapter Xvii - OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT]
[Part 1910 - OCCUPATIONAL SAFETY AND HEALTH STANDARDS]
[Subpart S - Electrical]
[Sec. 1910.303 - General requirements.]
[From the U.S. Government Printing Office]


29LABOR52002-07-012002-07-01falseGeneral requirements.1910.303Sec. 1910.303LABORRegulations Relating to Labor (Continued)OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION, DEPARTMENTOCCUPATIONAL SAFETY AND HEALTH STANDARDSElectrical
Sec. 1910.303  General requirements.

    (a) Approval. The conductors and equipment required or permitted by 
this subpart shall be acceptable only if approved.
    (b) Examination, installation, and use of equipment--(1) 
Examination. Electrical equipment shall be free from recognized hazards 
that are likely to cause death or serious physical harm to employees. 
Safety of equipment shall be determined using the following 
considerations:
    (i) Suitability for installation and use in conformity with the 
provisions of this subpart. Suitability of equipment for an identified 
purpose may be evidenced by listing or labeling for that identified 
purpose.
    (ii) Mechanical strength and durability, including, for parts 
designed to enclose and protect other equipment, the adequacy of the 
protection thus provided.
    (iii) Electrical insulation.
    (iv) Heating effects under conditions of use.
    (v) Arcing effects.
    (vi) Classification by type, size, voltage, current capacity, 
specific use.
    (vii) Other factors which contribute to the practical safeguarding 
of employees using or likely to come in contact with the equipment.
    (2) Installation and use. Listed or labeled equipment shall be used 
or installed in accordance with any instructions included in the listing 
or labeling.
    (c) Splices. Conductors shall be spliced or joined with splicing 
devices suitable for the use or by brazing, welding, or soldering with a 
fusible metal or alloy. Soldered splices shall first be so spliced or 
joined as to be mechanically and electrically secure without solder and 
then soldered. All splices and joints and the free ends of conductors 
shall be covered with an insulation equivalent to that of the conductors 
or with an insulating device suitable for the purpose.
    (d) Arcing parts. Parts of electric equipment which in ordinary 
operation produce arcs, sparks, flames, or molten metal shall be 
enclosed or separated and isolated from all combustible material.
    (e) Marking. Electrical equipment may not be used unless the 
manufacturer's name, trademark, or other descriptive marking by which 
the organization responsible for the product may be identified is placed 
on the equipment. Other markings shall be provided giving voltage, 
current, wattage, or other ratings as necessary. The marking shall be of 
sufficient durability to withstand the environment involved.
    (f) Identification of disconnecting means and circuits. Each 
disconnecting means required by this subpart for motors and appliances 
shall be legibly marked to indicate its purpose, unless located and 
arranged so the purpose is evident. Each service, feeder, and branch 
circuit, at its disconnecting means or overcurrent device, shall be 
legibly marked to indicate its purpose, unless located and arranged so 
the purpose is evident. These markings shall be of sufficient durability 
to withstand the environment involved.
    (g) 600 Volts, nominal, or less--(1) Working space about electric 
equipment. Sufficient access and working space

[[Page 838]]

shall be provided and maintained about all electric equipment to permit 
ready and safe operation and maintenance of such equipment.
    (i) Working clearances. Except as required or permitted elsewhere in 
this subpart, the dimension of the working space in the direction of 
access to live parts operating at 600 volts or less and likely to 
require examination, adjustment, servicing, or maintenance while alive 
may not be less than indicated in Table S-1. In addition to the 
dimensions shown in Table S-1, workspace may not be less than 30 inches 
wide in front of the electric equipment. Distances shall be measured 
from the live parts if they are exposed, or from the enclosure front or 
opening if the live parts are enclosed. Concrete, brick, or tile walls 
are considered to be grounded. Working space is not required in back of 
assemblies such as dead-front switchboards or motor control centers 
where there are no renewable or adjustable parts such as fuses or 
switches on the back and where all connections are accessible from 
locations other than the back.

                      Table S-1--Working Clearances
------------------------------------------------------------------------
                                                 Minimum clear distance
                                                 for condition\2\ (ft)
          Nominal voltage to ground           --------------------------
                                                 (a)      (b)      (c)
------------------------------------------------------------------------
0-150........................................    \1\ 3    \1\ 3        3
151-600......................................    \1\ 3   3\1/2\        4
------------------------------------------------------------------------
\1\ Minimum clear distances may be 2 feet 6 inches for installations
  built prior to April 16, 1981.
\2\ Conditions (a), (b), and (c), are as follows: (a) Exposed live parts
  on one side and no live or grounded parts on the other side of the
  working space, or exposed live parts on both sides effectively guarded
  by suitable wood or other insulating material. Insulated wire or
  insulated busbars operating at not over 300 volts are not considered
  live parts. (b) Exposed live parts on one side and grounded parts on
  the other side. (c) Exposed live parts on both sides of the workspace
  [not guarded as provided in Condition (a)] with the operator between.

    (ii) Clear spaces. Working space required by this subpart may not be 
used for storage. When normally enclosed live parts are exposed for 
inspection or servicing, the working space, if in a passageway or 
general open space, shall be suitably guarded.
    (iii) Access and entrance to working space. At least one entrance of 
sufficient area shall be provided to give access to the working space 
about electric equipment.
    (iv) Front working space. Where there are live parts normally 
exposed on the front of switchboards or motor control centers, the 
working space in front of such equipment may not be less than 3 feet.
    (v) Illumination. Illumination shall be provided for all working 
spaces about service equipment, switchboards, panelboards, and motor 
control centers installed indoors.
    (vi) Headroom. The minimum headroom of working spaces about service 
equipment, switchboards, panel-boards, or motor control centers shall be 
6 feet 3 inches.
    Note: As used in this section a motor control center is an assembly 
of one or more enclosed sections having a common power bus and 
principally containing motor control units.
    (2) Guarding of live parts. (i) Except as required or permitted 
elsewhere in this subpart, live parts of electric equipment operating at 
50 volts or more shall be guarded against accidental contact by approved 
cabinets or other forms of approved enclosures, or by any of the 
following means:
    (A) By location in a room, vault, or similar enclosure that is 
accessible only to qualified persons.
    (B) By suitable permanent, substantial partitions or screens so 
arranged that only qualified persons will have access to the space 
within reach of the live parts. Any openings in such partitions or 
screens shall be so sized and located that persons are not likely to 
come into accidental contact with the live parts or to bring conducting 
objects into contact with them.
    (C) By location on a suitable balcony, gallery, or platform so 
elevated and arranged as to exclude unqualified persons.
    (D) By elevation of 8 feet or more above the floor or other working 
surface.
    (ii) In locations where electric equipment would be exposed to 
physical damage, enclosures or guards shall be so arranged and of such 
strength as to prevent such damage.
    (iii) Entrances to rooms and other guarded locations containing 
exposed live parts shall be marked with conspicuous warning signs 
forbidding unqualified persons to enter.
    (h) Over 600 volts, nominal--(1) General. Conductors and equipment 
used on circuits exceeding 600 volts, nominal,

[[Page 839]]

shall comply with all applicable provisions of paragraphs (a) through 
(g) of this section and with the following provisions which supplement 
or modify those requirements. The provisions of paragraphs (h)(2), 
(h)(3), and (h)(4) of this section do not apply to equipment on the 
supply side of the service conductors.
    (2) Enclosure for electrical installations. Electrical installations 
in a vault, room, closet or in an area surrounded by a wall, screen, or 
fence, access to which is controlled by lock and key or other approved 
means, are considered to be accessible to qualified persons only. A 
wall, screen, or fence less than 8 feet in height is not considered to 
prevent access unless it has other features that provide a degree of 
isolation equivalent to an 8 foot fence. The entrances to all buildings, 
rooms, or enclosures containing exposed live parts or exposed conductors 
operating at over 600 volts, nominal, shall be kept locked or shall be 
under the observation of a qualified person at all times.
    (i) Installations accessible to qualified persons only. Electrical 
installations having exposed live parts shall be accessible to qualified 
persons only and shall comply with the applicable provisions of 
paragraph (h)(3) of this section.
    (ii) Installations accessible to unqualified persons. Electrical 
installations that are open to unqualified persons shall be made with 
metal-enclosed equipment or shall be enclosed in a vault or in an area, 
access to which is controlled by a lock. If metal-enclosed equipment is 
installed so that the bottom of the enclosure is less than 8 feet above 
the floor, the door or cover shall be kept locked. Metal-enclosed 
switchgear, unit substations, transformers, pull boxes, connection 
boxes, and other similar associated equipment shall be marked with 
appropriate caution signs. If equipment is exposed to physical damage 
from vehicular traffic, suitable guards shall be provided to prevent 
such damage. Ventilating or similar openings in metal-enclosed equipment 
shall be designed so that foreign objects inserted through these 
openings will be deflected from energized parts.
    (3) Workspace about equipment. Sufficient space shall be provided 
and maintained about electric equipment to permit ready and safe 
operation and maintenance of such equipment. Where energized parts are 
exposed, the minimum clear workspace may not be less than 6 feet 6 
inches high (measured vertically from the floor or platform), or less 
than 3 feet wide (measured parallel to the equipment). The depth shall 
be as required in Table S-2. The workspace shall be adequate to permit 
at least a 90-degree opening of doors or hinged panels.
    (i) Working space. The minimum clear working space in front of 
electric equipment such as switchboards, control panels, switches, 
circuit breakers, motor controllers, relays, and similar equipment may 
not be less than specified in Table S-2 unless otherwise specified in 
this subpart. Distances shall be measured from the live parts if they 
are exposed, or from the enclosure front or opening if the live parts 
are enclosed. However, working space is not required in back of 
equipment such as deadfront switchboards or control assemblies where 
there are no renewable or adjustable parts (such as fuses or switches) 
on the back and where all connections are accessible from locations 
other than the back. Where rear access is required to work on de-
energized parts on the back of enclosed equipment, a minimum working 
space of 30 inches horizontally shall be provided.

  Table S-2--Minimum Depth of Clear Working Space in Front of Electric
                                Equipment
------------------------------------------------------------------------
                                                  Conditions \2\ (ft)
          Nominal voltage to ground           --------------------------
                                                 (a)      (b)      (c)
------------------------------------------------------------------------
601 to 2,500.................................        3        4        5
2,501 to 9,000...............................        4        5        6
9,001 to 25,000..............................        5        6        9
25,001 to 75kV \1\...........................        6        8       10
Above 75kV \1\...............................        8       10       12
------------------------------------------------------------------------
\1\ Minimum depth of clear working space in front of electric equipment
  with a nominal voltage to ground above 25,000 volts may be the same as
  for 25,000 volts under Conditions (a), (b), and (c) for installations
  built prior to April 16, 1981.
\2\ Conditions (a), (b), and (c) are as follows: (a) Exposed live parts
  on one side and no live or grounded parts on the other side of the
  working space, or exposed live parts on both sides effectively guarded
  by suitable wood or other insulating materials. Insulated wire or
  insulated busbars operating at not over 300 volts are not considered
  live parts. (b) Exposed live parts on one side and grounded parts on
  the other side. Concrete, brick, or tile walls will be considered as
  grounded surfaces. (c) Exposed live parts on both sides of the
  workspace not guarded as provided in Condition (a) with the operator
  between.


[[Page 840]]

    (ii) Illumination. Adequate illumination shall be provided for all 
working spaces about electric equipment. The lighting outlets shall be 
so arranged that persons changing lamps or making repairs on the 
lighting system will not be endangered by live parts or other equipment. 
The points of control shall be so located that persons are not likely to 
come in contact with any live part or moving part of the equipment while 
turning on the lights.
    (iii) Elevation of unguarded live parts. Unguarded live parts above 
working space shall be maintained at elevations not less than specified 
in Table S-3.

  Table S-3--Elevation of Unguarded Energized Parts Above Working Space
------------------------------------------------------------------------
      Nominal voltage between phases              Minimum elevation
------------------------------------------------------------------------
601 to 7,500..............................  *8 feet 6 inches.
7,501 to 35,000...........................  9 feet.
Over 35kV.................................  9 feet + 0.37 inches per kV
                                             above 35kV.
------------------------------------------------------------------------
*Note.--Minimum elevation may be 8 feet 0 inches for installations built
  prior to April 16, 1981 if the nominal voltage between phases is in
  the range of 601-6600 volts.

    (4) Entrance and access to workspace. (See Sec. 1910.302(b)(3).)
    (i) At least one entrance not less than 24 inches wide and 6 feet 6 
inches high shall be provided to give access to the working space about 
electric equipment. On switchboard and control panels exceeding 48 
inches in width, there shall be one entrance at each end of such board 
where practicable. Where bare energized parts at any voltage or 
insulated energized parts above 600 volts are located adjacent to such 
entrance, they shall be suitably guarded.
    (ii) Permanent ladders or stairways shall be provided to give safe 
access to the working space around electric equipment installed on 
platforms, balconies, mezzanine floors, or in attic or roof rooms or 
spaces.

[46 FR 4056, Jan. 16, 1981; 46 FR 40185, Aug. 7, 1981]