[Title 29 CFR 1910.28]
[Code of Federal Regulations (annual edition) - July 1, 2002 Edition]
[Title 29 - LABOR]
[Subtitle B - Regulations Relating to Labor (Continued)]
[Chapter Xvii - OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT]
[Part 1910 - OCCUPATIONAL SAFETY AND HEALTH STANDARDS]
[Subpart D - Walking-Working Surfaces]
[Sec. 1910.28 - Safety requirements for scaffolding.]
[From the U.S. Government Printing Office]


29LABOR52002-07-012002-07-01falseSafety requirements for scaffolding.1910.28Sec. 1910.28LABORRegulations Relating to Labor (Continued)OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION, DEPARTMENTOCCUPATIONAL SAFETY AND HEALTH STANDARDSWalking-Working Surfaces
Sec. 1910.28  Safety requirements for scaffolding.

    (a) General requirements for all scaffolds. (1) Scaffolds shall be 
furnished and erected in accordance with this standard for persons 
engaged in work that cannot be done safely from the ground or from solid 
construction, except that ladders used for such work shall conform to 
Sec. 1910.25 and Sec. 1910.26.
    (2) The footing or anchorage for scaffolds shall be sound, rigid, 
and capable of carrying the maximum intended load without settling or 
displacement. Unstable objects such as barrels, boxes, loose brick, or 
concrete blocks shall not be used to support scaffolds or planks.
    (3) [Reserved]
    (4) Scaffolds and their components shall be capable of supporting 
without failure at least four times the maximum intended load.
    (5) Scaffolds and other devices mentioned or described in this 
section shall be maintained in safe condition. Scaffolds shall not be 
altered or moved horizontally while they are in use or occupied.
    (6) Any scaffold damaged or weakened from any cause shall be 
immediately repaired and shall not be used until repairs have been 
completed.
    (7) Scaffolds shall not be loaded in excess of the working load for 
which they are intended.
    (8) All load-carrying timber members of scaffold framing shall be a 
minimum of 1,500 f. (Stress Grade) construction grade lumber. All 
dimensions are nominal sizes as provided in the American Lumber 
Standards, except that where rough sizes are noted, only rough or 
undressed lumber of the size specified will satisfy minimum 
requirements. (Note: Where nominal sizes of lumber are used in place of 
rough sizes, the nominal size lumber shall be such as to provide 
equivalent strength to that specified in tables D-7 through D-12 and D-
16.)
    (9) All planking shall be Scaffold Grade as recognized by grading 
rules for the species of wood used. The maximum permissible spans for 2- 
x 9-inch or wider planks are shown in the following table:

[[Page 133]]



------------------------------------------------------------------------
                                                 Material
                                 ---------------------------------------
                                      Full thickness          Nominal
                                     undressed lumber        thickness
                                 ------------------------     lumber
                                                         ---------------
 
------------------------------------------------------------------------
Working load (p.s.f.)...........      25      50      75      25      50
Permissible span (ft.)..........      10       8       6       8       9
------------------------------------------------------------------------


The maximum permissible span for 1\1/4\ x 9-inch or wider plank of full 
thickness is 4 feet with medium loading of 50 p.s.f.
    (10) Nails or bolts used in the construction of scaffolds shall be 
of adequate size and in sufficient numbers at each connection to develop 
the designed strength of the scaffold. Nails shall not be subjected to a 
straight pull and shall be driven full length.
    (11) All planking or platforms shall be overlapped (minimum 12 
inches) or secured from movement.
    (12) An access ladder or equivalent safe access shall be provided.
    (13) Scaffold planks shall extend over their end supports not less 
than 6 inches nor more than 18 inches.
    (14) The poles, legs, or uprights of scaffolds shall be plumb, and 
securely and rigidly braced to prevent swaying and displacement.
    (15) Materials being hoisted onto a scaffold shall have a tag line.
    (16) Overhead protection shall be provided for men on a scaffold 
exposed to overhead hazards.
    (17) Scaffolds shall be provided with a screen between the toeboard 
and the guardrail, extending along the entire opening, consisting of No. 
18 gauge U.S. Standard Wire one-half-inch mesh or the equivalent, where 
persons are required to work or pass under the scaffolds.
    (18) Employees shall not work on scaffolds during storms or high 
winds.
    (19) Employees shall not work on scaffolds which are covered with 
ice or snow, unless all ice or snow is removed and planking sanded to 
prevent slipping.
    (20) Tools, materials, and debris shall not be allowed to accumulate 
in quantities to cause a hazard.
    (21) Only treated or protected fiber rope shall be used for or near 
any work involving the use of corrosive substances or chemicals.
    (22) Wire or fiber rope used for scaffold suspension shall be 
capable of supporting at least six times the intended load.
    (23) When acid solutions are used for cleaning buildings over 50 
feet in height, wire rope supported scaffolds shall be used.
    (24) The use of shore scaffolds or lean-to scaffolds is prohibited.
    (25) Lumber sizes, when used in this section, refer to nominal sizes 
except where otherwise stated.
    (26) Scaffolds shall be secured to permanent structures, through use 
of anchor bolts, reveal bolts, or other equivalent means. Window 
cleaners' anchor bolts shall not be used.
    (27) Special precautions shall be taken to protect scaffold members, 
including any wire or fiber ropes, when using a heat-producing process.
    (b) General requirements for wood pole scaffolds. (1) Scaffold poles 
shall bear on a foundation of sufficient size and strength to spread the 
load from the poles over a sufficient area to prevent settlement. All 
poles shall be set plumb.
    (2) Where wood poles are spliced, the ends shall be squared and the 
upper section shall rest squarely on the lower section. Wood splice 
plates shall be provided on at least two adjacent sides and shall not be 
less than 4 feet 0 inches in length, overlapping the abutted ends 
equally, and have the same width and not less than the cross-sectional 
area of the pole. Splice plates of other materials of equivalent 
strength may be used.
    (3) Independent pole scaffolds shall be set as near to the wall of 
the building as practicable.
    (4) All pole scaffolds shall be securely guyed or tied to the 
building or structure. Where the height or length exceeds 25 feet, the 
scaffold shall be secured at intervals not greater than 25 feet 
vertically and horizontally.
    (5) Putlogs or bearers shall be set with their greater dimensions 
vertical, long enough to project over the ledgers of the inner and outer 
rows of poles at least 3 inches for proper support.
    (6) Every wooden putlog on single pole scaffolds shall be reinforced 
with a

[[Page 134]]

\3/16\ x 2-inch steel strip or equivalent secured to its lower edge 
throughout its entire length.
    (7) Ledgers shall be long enough to extend over two pole spaces. 
Ledgers shall not be spliced between the poles. Ledgers shall be 
reinforced by bearing blocks securely nailed to the side of the pole to 
form a support for the ledger.
    (8) Diagonal bracing shall be provided to prevent the poles from 
moving in a direction parallel with the wall of the building, or from 
buckling.
    (9) Cross bracing shall be provided between the inner and outer sets 
of poles in independent pole scaffolds. The free ends of pole scaffolds 
shall be cross braced.
    (10) Full diagonal face bracing shall be erected across the entire 
face of pole scaffolds in both directions. The braces shall be spliced 
at the poles.
    (11) Platform planks shall be laid with their edges close together 
so the platform will be tight with no spaces through which tools or 
fragments of material can fall.
    (12) Where planking is lapped, each plank shall lap its end supports 
at least 12 inches. Where the ends of planks abut each other to form a 
flush floor, the butt joint shall be at the centerline of a pole. The 
abutted ends shall rest on separate bearers. Intermediate beams shall be 
provided where necessary to prevent dislodgment of planks due to 
deflection, and the ends shall be nailed or cleated to prevent their 
dislodgment.
    (13) When a scaffold turns a corner, the platform planks shall be 
laid to prevent tipping. The planks that meet the corner putlog at an 
angle shall be laid first, extending over the diagonally placed putlog 
far enough to have a good safe bearing, but not far enough to involve 
any danger from tipping. The planking running in the opposite direction 
at right angles shall be laid so as to extend over and rest on the first 
layer of planking.
    (14) When moving platforms to the next level, the old platform shall 
be left undisturbed until the new putlogs or bearers have been set in 
place, ready to receive the platform planks.
    (15) Guardrails not less than 2 x 4 inches or the equivalent and not 
less than 36 inches or more than 42 inches high, with a mid-rail, when 
required, of 1 x 4-inch lumber or equivalent, and toeboards, shall be 
installed at all open sides on all scaffolds more than 10 feet above the 
ground or floor. Toeboards shall be a minimum of 4 inches in height. 
Wire mesh shall be installed in accordance with paragraph (a)(17) of 
this section.
    (16) All wood pole scaffolds 60 feet or less in height shall be 
constructed and erected in accordance with tables D-7 through D-12 of 
this section. If they are over 60 feet in height they shall be designed 
by a registered professional engineer and constructed and erected in 
accordance with such design. A copy of the typical drawings and 
specifications shall be made available to the employer and for 
inspection purposes.
    (17) Wood-pole scaffolds shall not be erected beyond the reach of 
effective firefighting apparatus.

Table D-7--Minimum Nominal Size and Maximum Spacing of Members of Single
                       Pole Scaffolds--Light Duty
------------------------------------------------------------------------
                                        Maximum height of scaffold
                                ----------------------------------------
                                       20 feet              60 feet
------------------------------------------------------------------------
Uniformly distributed load.....  Not to exceed 25
                                  pounds per square
                                  foot..
Poles or uprights..............  2 by 4 in..........  4 by 4 in.
Pole spacing (longitudinal)....  6 ft. 0 in.........  10 ft. 0 in.
Maximum width of scaffold......  5 ft. 0 in.........  5 ft. 0 in.
Bearers or putlogs to 3 ft. 0    2 by 4 in..........  2 by 4 in.
 in. width.
Bearers or putlogs to 5 ft. 0    2 by 6 in. or 3 by   2 by 6 in. or 3 by
 in. width.                       4 in.                4 in.(rough).
Ledgers........................  1 by 4 in..........  1\1/4\ by 9 in.
Planking.......................  1\1/4\ by 9 in.      2 by 9 in.
                                  (rough).
Vertical spacing of horizontal   7 ft. 0 in.........  7 ft. 0 in.
 members.
Bracing, horizontal and          1 by 4 in..........  1 by 4 in.
 diagonal.
Tie-ins........................  1 by 4 in..........  1 by 4 in.
Toeboards......................  4 in. high           4 in. high
                                  (minimum).           (minimum).

[[Page 135]]

 
Guardrail......................  2 by 4 in..........  2 by 4 in.
------------------------------------------------------------------------
All members except planking are used on edge.


Table D-8--Minimum Nominal Size and Maximum Spacing of Members of Single
                       Pole Scaffolds--Medium Duty
Uniformly distributed load................  Not to exceed 50 pounds per
                                             square foot.
Maximum height of scaffold................  60 ft.
Poles or uprights.........................  4 by 4 in.
Pole spacing (longitudinal)...............  8 ft. 0 in.
Maximum width of scaffold.................  5 ft. 0 in.
Bearers or putlogs........................  2 by 9 in. or 3 by 4 in.
Spacing of bearers or putlogs.............  8 ft. 0 in.
Ledgers...................................  2 by 9 in.
Vertical spacing of horizontal members....  9 ft. 0 in.
Bracing, horizontal.......................  1 by 6 in. or 1\1/4\ by 4
                                             in.
Bracing, diagonal.........................  1 by 4 in.
Tie-ins...................................  1 by 4 in.
Planking..................................  2 by 9 in.
Toeboards.................................  4 in. high (minimum).
Guardrail.................................  2 by 4 in.
------------------------------------------------------------------------
All members except planking are used on edge.


Table D-9--Minimum Nominal Size and Maximum Spacing of Members of Single
                       Pole Scaffolds--Heavy Duty
Uniformly distributed load................  Not to exceed 75 pounds per
                                             square foot.
Maximum height of scaffold................  60 ft.
Poles or uprights.........................  4 by 4 in.
Pole spacing (longitudinal)...............  6 ft. 0 in.
Maximum width of scaffold.................  5 ft. 0 in.
Bearers or putlogs........................  2 by 9 in. or 3 by 5 in.
                                             (rough).
Spacing of bearers or putlogs.............  6 ft. 0 in.
Ledgers...................................  2 by 9 in.
Vertical spacing of horizontal members....  6 ft. 6 in.
Bracing, horizontal and diagonal..........  2 by 4 in.
Tie-ins...................................  1 by 4 in.
Planking..................................  2 by 9 in.
Toeboards.................................  4 in. high (minimum).
Guardrail.................................  2 by 4 in.
------------------------------------------------------------------------
All members except planking are used on edge.


   Table D-10--Minimum Nominal Size and Maximum Spacing of Members of
                 Independent Pole Scaffolds--Light Duty
------------------------------------------------------------------------
                                        Maximum height of scaffold
                                ----------------------------------------
                                       20 feet              60 feet
------------------------------------------------------------------------
Uniformly distributed load.....  Not to exceed 25
                                  pounds per square
                                  foot..
Poles or uprights..............  2 by 4 in..........  4 by 4 in.
Pole spacing (longitudinal)....  6 ft. 0 in.........  10 ft. 0 in.
Pole spacing (transverse)......  6 ft. 0 in.........  10 ft. 0 in.
Ledgers........................  1\1/4\ by 4 in.....  1\1/4\ by 9 in.
Bearers to 3 ft. 0 in. span....  2 by 4 in..........  2 by 4 in.
Bearers to 10 ft. 0 in. span...  2 by 6 in. or 3 by   2 by 9 (rough) or
                                  4 in.                3 by 8 in.
Planking.......................  1\1/4\ by 9 in.....  2 by 9 in.
Vertical spacing of horizontal   7 ft. 0 in.........  7 ft. 0 in.
 members.
Bracing, horizontal and          1 by 4 in..........  1 by 4 in.
 diagonal.
Tie-ins........................  1 by 4 in..........  1 by 4 in.
Toeboards......................  4 in. high.........  4 in. high
                                                       (minimum).
Guardrail......................  2 by 4 in..........  2 by 4 in.
------------------------------------------------------------------------
All members except planking are used on edge.


   Table D-11--Minimum Nominal Size and Maximum Spacing of Members of
                 Independent Pole Scaffolds--Medium Duty
Uniformly distributed load................  Not to exceed 50 pounds per
                                             square foot.
Maximum height of scaffold................  60 ft.
Poles or uprights.........................  4 by 4 in.
Pole spacing (longitudinal)...............  8 ft. 0 in.
Pole spacing (transverse).................  8 ft. 0 in.
Ledgers...................................  2 by 9 in.
Vertical spacing of horizontal members....  6 ft. 0 in.
Spacing of bearers........................  8 ft. 0 in.
Bearers...................................  2 by 9 in. (rough) or 2 by
                                             10 in.
Bracing, horizontal.......................  1 by 6 in. or 1\1/4\ by 4
                                             in.
Bracing, diagonal.........................  1 by 4 in.
Tie-ins...................................  1 by 4 in.
Planking..................................  2 by 9 in.
Toeboards.................................  4 in. high (minimum).
Guardrail.................................  2 by 4 in.
------------------------------------------------------------------------
All members except planking are used on edge.


[[Page 136]]


   Table D-12--Minimum Nominal Size and Maximum Spacing of Members of
                 Independent Pole Scaffolds--Heavy Duty
Uniformly distributed load................  Not to exceed 75 pounds per
                                             square foot.
Maximum height of scaffold................  60 ft.
Poles or uprights.........................  4 by 4 in.
Pole spacing (longitudinal)...............  6 ft. 0 in.
Pole spacing (transverse).................  8 ft. 0 in.
Ledgers...................................  2 by 9 in.
Vertical spacing of horizontal members....  4 ft. 6 in.
Bearers...................................  2 by 9 in. (rough).
Bracing, horizontal and diagonal..........  2 by 4 in.
Tie-ins...................................  1 by 4 in.
Planking..................................  2 by 9 in.
Toeboards.................................  4 in. high (minimum).
Guardrail.................................  2 by 4 in.
------------------------------------------------------------------------
All members except planking are used on edge.


           Table D-13--Tube and Coupler Scaffolds--Light Duty
Uniformly distributed load................  Not to exceed 25 p.s.f.
post spacing (longitudinal)...............  10 ft. 0 in.
Post spacing (transverse).................  6 ft. 0 in.
------------------------------------------------------------------------


------------------------------------------------------------------------
                            Additional planked
     Working levels               levels              Maximum height
------------------------------------------------------------------------
                1                        8                 125 ft.
                2                        4                 125 ft.
                3                        0            91 ft. 0 in.
------------------------------------------------------------------------


           Table D-14--Tube and Coupler Scaffolds--Medium Duty
Uniformly distributed load................  Not to exceed 50 p.s.f.
Post spacing (longitudinal)...............  8 ft. 0 in.
Post spacing (transverse).................  6 ft. 0 in.
------------------------------------------------------------------------


------------------------------------------------------------------------
                            Additional planked
     Working levels               levels              Maximum height
------------------------------------------------------------------------
                1                        6                 125 ft.
                2                        0            78 ft. 0 in.
------------------------------------------------------------------------


           Table D-15--Tube and Coupler Scaffolds--Heavy Duty
Uniformly distributed load................  Not to exceed 75 p.s.f.
Post spacing (longitudinal)...............  6 ft. 6 in.
Post spacing (transverse).................  6 ft. 0 in.
------------------------------------------------------------------------


------------------------------------------------------------------------
                            Additional planked
     Working levels               levels              Maximum height
------------------------------------------------------------------------
                1                        6                 125 ft.
------------------------------------------------------------------------

    (c) Tube and coupler scaffolds. (1) A light-duty tube and coupler 
scaffold shall have all posts, bearers, runners, and bracing of nominal 
2-inch O.D. steel tubing. The posts shall be spaced no more than 6 feet 
apart by 10 feet along the length of the scaffold. Other structural 
metals when used must be designed to carry an equivalent load.
    (2) A medium-duty tube and coupler scaffold shall have all posts, 
runners, and bracing of nominal 2-inch O.D. steel tubing. Posts spaced 
not more than 6 feet apart by 8 feet along the length of the scaffold 
shall have bearers of nominal 2\1/2\-inch O.D. steel tubing. Posts 
spaced not more than 5 feet apart by 8 feet along the length of the 
scaffold shall have bearers of nominal 2-inch O.D. steel tubing. Other 
structural metals when used must be designed to carry an equivalent 
load.
    (3) A heavy-duty tube and coupler scaffold shall have all posts, 
runners, and bracing of nominal 2-inch O.D. steel tubing, with the posts 
spaced not more than 6 feet apart by 6 feet 6 inches along the length of 
the scaffold. Other structural metals when used must be designed to 
carry an equivalent load.
    (4) Tube and coupler scaffolds shall be limited in heights and 
working levels to those permitted in tables D-13, 14, and 15, of this 
section. Drawings and specifications of all tube and coupler scaffolds 
above the limitations in tables D-13, 14, and 15 of this section shall 
be designed by a registered professional engineer and copies made 
available to the employer and for inspection purposes.
    (5) All tube and coupler scaffolds shall be constructed and erected 
to support four times the maximum intended loads as set forth in tables 
D-13, 14, and 15 of this section, or as set forth in the specifications 
by a registered professional engineer, copies which shall be made 
available to the employer and for inspection purposes.
    (6) All tube and coupler scaffolds shall be erected by competent and 
experienced personnel.
    (7) Posts shall be accurately spaced, erected on suitable bases, and 
maintained plumb.
    (8) Runners shall be erected along the length of the scaffold 
located on both the inside and the outside posts at even height. Runners 
shall be interlocked to form continuous lengths and coupled to each 
post. The bottom runners shall be located as close to the base as 
possible. Runners shall be placed not more than 6 feet 6 inches on 
centers.

[[Page 137]]

    (9) Bearers shall be installed transversely between posts and shall 
be securely coupled to the posts bearing on the runner coupler. When 
coupled directly to the runners, the coupler must be kept as close to 
the posts as possible.
    (10) Bearers shall be at least 4 inches but not more than 12 inches 
longer than the post spacing or runner spacing. Bearers may be 
cantilevered for use as brackets to carry not more than two planks.
    (11) Cross bracing shall be installed across the width of the 
scaffold at least every third set of posts horizontally and every fourth 
runner vertically. Such bracing shall extend diagonally from the inner 
and outer runners upward to the next outer and inner runners.
    (12) Longitudinal diagonal bracing shall be installed at 
approximately a 45-degree angle from near the base of the first outer 
post upward to the extreme top of the scaffold. Where the longitudinal 
length of the scaffold permits, such bracing shall be duplicated 
beginning at every fifth post. In a similar manner, longitudinal 
diagonal bracing shall also be installed from the last post extending 
back and upward toward the first post. Where conditions preclude the 
attachment of this bracing to the posts, it may be attached to the 
runners.
    (13) The entire scaffold shall be tied to and securely braced 
against the building at intervals not to exceed 30 feet horizontally and 
26 feet vertically.
    (14) Guardrails not less than 2x4 inches or the equivalent and not 
less than 36 inches or more than 42 inches high, with a mid-rail, when 
required, of 1x4-inch lumber or equivalent, and toeboards, shall be 
installed at all open sides on all scaffolds more than 10 feet above the 
ground or floor. Toeboards shall be a minimum of 4 inches in height. 
Wire mesh shall be installed in accordance with paragraph (a)(17) of 
this section.
    (d) Tubular welded frame scaffolds. (1) Metal tubular frame 
scaffolds, including accessories such as braces, brackets, trusses, 
screw legs, ladders, etc., shall be designed and proved to safely 
support four times the maximum intended load.
    (2) Spacing of panels or frames shall be consistent with the loads 
imposed.
    (3) Scaffolds shall be properly braced by cross bracing or diagonal 
braces, or both, for securing vertical members together laterally, and 
the cross braces shall be of such length as will automatically square 
and aline vertical members so that the erected scaffold is always plumb, 
square, and rigid. All brace connections shall be made secure.
    (4) Scaffold legs shall be set on adjustable bases or plain bases 
placed on mud sills or other foundations adequate to support the maximum 
intended load.
    (5) The frames shall be placed one on top of the other with coupling 
or stacking pins to provide proper vertical alinement of the legs.
    (6) Where uplift may occur, panels shall be locked together 
vertically by pins or other equivalent suitable means.
    (7) Guardrails not less than 2 x 4 inches or the equivalent and not 
less than 36 inches or more than 42 inches high, with a mid-rail, when 
required, of 1- x 4-inch lumber or equivalent, and toeboards, shall be 
installed at all open sides on all scaffolds more than 10 feet above the 
ground or floor. Toeboards shall be a minimum of 4 inches in height. 
Wire mesh shall be installed in accordance with paragraph (a)(17) of 
this section.
    (8) All tubular metal scaffolds shall be constructed and erected to 
support four times the maximum intended loads.
    (9) To prevent movement, the scaffold shall be secured to the 
building or structure at intervals not to exceed 30 feet horizontally 
and 26 feet vertically.
    (10) Maximum permissible spans of planking shall be in conformity 
with paragraph (a)(9) of this section.
    (11) Drawings and specifications for all frame scaffolds over 125 
feet in height above the base plates shall be designed by a registered 
professional engineer and copies made available to the employer and for 
inspection purposes.
    (12) All tubular welded frame scaffolds shall be erected by 
competent and experienced personnel.

[[Page 138]]

    (13) Frames and accessories for scaffolds shall be maintained in 
good repair and every defect, unsafe condition, or noncompliance with 
this section shall be immediately corrected before further use of the 
scaffold. Any broken, bent, excessively rusted, altered, or otherwise 
structurally damaged frames or accessories shall not be used.
    (14) Periodic inspections shall be made of all welded frames and 
accessories, and any maintenance, including painting, or minor 
corrections authorized by the manufacturer, shall be made before further 
use.
    (e) Outrigger scaffolds. (1) Outrigger beams shall extend not more 
than 6 feet beyond the face of the building. The inboard end of 
outrigger beams, measured from the fulcrum point to the extreme point of 
support, shall be not less than one and one-half times the outboard end 
in length. The beams shall rest on edge, the sides shall be plumb, and 
the edges shall be horizontal. The fulcrum point of the beam shall rest 
on a secure bearing at least 6 inches in each horizontal dimension. The 
beam shall be secured in place against movement and shall be securely 
braced at the fulcrum point against tipping.
    (2) The inboard ends of outrigger beams shall be securely supported 
either by means of struts bearing against sills in contact with the 
overhead beams or ceiling, or by means of tension members secured to the 
floor joists underfoot, or by both if necessary. The inboard ends of 
outrigger beams shall be secured against tipping and the entire 
supporting structure shall be securely braced in both directions to 
prevent any horizontal movement.
    (3) Unless outrigger scaffolds are designed by a licensed 
professional engineer, they shall be constructed and erected in 
accordance with table D-16. Outrigger scaffolds designed by a registered 
professional engineer shall be constructed and erected in accordance 
with such design. A copy of the detailed drawings and specifications 
showing the sizes and spacing of members shall be kept on the job.
    (4) Planking shall be laid tight and shall extend to within 3 inches 
of the building wall. Planking shall be nailed or bolted to outriggers.
    (5) Where there is danger of material falling from the scaffold, a 
wire mesh or other enclosure shall be provided between the guardrail and 
the toeboard.
    (6) Where additional working levels are required to be supported by 
the outrigger method, the plans and specifications of the outrigger and 
scaffolding structure shall be designed by a registered professional 
engineer.
    (f) Masons' adjustable multiple-point suspension scaffolds. (1) The 
scaffold shall be capable of sustaining a working load of 50 pounds per 
square foot and shall not be loaded in excess of that figure.
    (2) The scaffold shall be provided with hoisting machines that meet 
the requirements of a nationally recognized testing laboratory. Refer to 
Sec. 1910.7 for definition of nationally recognized testing laboratory.

   Table D-16--Minimum Nominal Size and Maximum Spacing of Members of
                           Outrigger Scaffolds
------------------------------------------------------------------------
                                      Light duty          Medium duty
------------------------------------------------------------------------
Maximum scaffold load...........  25 p.s.f..........  50 p.s.f.
Outrigger size..................  2 x 10 in.........  3 x 10 in.
Maximum outrigger spacing.......  10 ft 0 in........  6 ft 0 in.
Planking........................  2 x 9 in..........  2 x 9 in.
Guardrail.......................  2 x 4 in..........  2 x 4 in.
Guardrail uprights..............  2 x 4 in..........  2 x 4 in.
Toeboards (minimum).............  4 in..............  4 in.
------------------------------------------------------------------------

    (3) The platform shall be supported by wire ropes in conformity with 
paragraph (a)(22) of this section, suspended from overhead outrigger 
beams.
    (4) The scaffold outrigger beams shall consist of structural metal 
securely fastened or anchored to the frame or floor system of the 
building or structure.
    (5) Each outrigger beam shall be equivalent in strength to at least 
a standard 7-inch, 15.3-pound steel I-beam, be at least 15 feet long, 
and shall not project more than 6 feet 6 inches beyond the bearing 
point.
    (6) Where the overhang exceeds 6 feet 6 inches, outrigger beams 
shall be composed of stronger beams or multiple beams and be installed 
in accordance with approved designs and instructions.

[[Page 139]]

    (7) If channel iron outrigger beams are used in place of I-beams, 
they shall be securely fastened together with the flanges turned out.
    (8) All outrigger beams shall be set and maintained with their webs 
into vertical position.
    (9) A stop bolt shall be placed at each end of every outrigger beam.
    (10) The outrigger beam shall rest on suitable wood-bearing blocks.
    (11) All parts of the scaffold such as bolts, nuts, fittings, 
clamps, wire rope, and outrigger beams and their fastenings, shall be 
maintained in sound and good working condition and shall be inspected 
before each installation and periodically thereafter.
    (12) The free end of the suspension wire ropes shall be equipped 
with proper size thimbles and be secured by splicing or other equivalent 
means. The running ends shall be securely attached to the hoisting drum 
and at least four turns of rope shall at all times remain on the drum.
    (13) Where a single outrigger beam is used, the steel shackles or 
clevises with which the wire ropes are attached to the outrigger beams 
shall be placed directly over the hoisting drums.
    (14) The scaffold platform shall be equivalent in strength to at 
least 2-inch planking. (For maximum planking spans see paragraph (a)(9) 
of this section.)
    (15) Guardrails not less than 2 x 4 inches or the equivalent and not 
less than 36 inches or more than 42 inches high, with a mid-rail, when 
required, of 1 x 4-inch lumber or equivalent, and toeboards, shall be 
installed at all open sides on all scaffolds more than 10 feet above the 
ground or floor. Toeboards shall be a minimum of 4 inches in height. 
Wire mesh shall be installed in accordance with paragraph (a)(17) of 
this section.
    (16) Overhead protection shall be provided on the scaffold, not more 
than 9 feet above the platform, consisting of 2-inch planking or 
material of equivalent strength laid tight, when men are at work on the 
scaffold and an overhead hazard exists.
    (17) Each scaffold shall be installed or relocated in accordance 
with designs and instructions, of a registered professional engineer, 
and supervised by a competent, designated person.
    (g) Two-point suspension scaffolds (swinging scaffolds). (1) Two-
point suspension scaffold platforms shall be not less than 20 inches no 
more than 36 inches wide overall. The platform shall be securely 
fastened to the hangers by U-bolts or by other equivalent means.
    (2) The hangers of two-point suspension scaffolds shall be made of 
wrought iron, mild steel, or other equivalent material having a cross-
sectional area capable of sustaining four times the maximum intended 
load, and shall be designed with a support for guardrail, intermediate 
rail, and toeboard.
    (3) When hoisting machines are used on two-point suspension 
scaffolds, such machines shall be of a design tested and approved by a 
nationally recognized testing laboratory. Refer to Sec. 1910.7 for 
definition of nationally recognized testing laboratory.
    (4) The roof irons or hooks shall be of wrought iron, mild steel, or 
other equivalent material of proper size and design, securely installed 
and anchored. Tie-backs of three-fourth inch manila rope or the 
equivalent shall serve as a secondary means of anchorage, installed at 
right angles to the face of the building whenever possible and secured 
to a structurally sound portion of the building.
    (5) Guardrails not less than 2 x 4 inches or the equivalent and not 
less than 36 inches or more than 42 inches high, with a mid-rail, when 
required, of 1- x 4-inch lumber or equivalent, and toeboards, shall be 
installed at all open sides on all scaffolds more than 10 feet above the 
ground or floor. Toeboards shall be a minimum of 4 inches in height. 
Wire mesh shall be installed in accordance with paragraph (a)(17) of 
this section.
    (6) Two-point suspension scaffolds shall be suspended by wire or 
fiber ropes. Wire and fiber ropes shall conform to paragraph (a)(22) of 
this section.
    (7) The blocks for fiber ropes shall be of standard 6-inch size, 
consisting of at least one double and one single block. The sheaves of 
all blocks shall fit the size of rope used.

[[Page 140]]

    (8) All wire ropes, fiber ropes, slings, hangers, platforms, and 
other supporting parts shall be inspected before every installation. 
Periodic inspections shall be made while the scaffold is in use.
    (9) On suspension scaffolds designed for a working load of 500 
pounds no more than two men shall be permitted to work at one time. On 
suspension scaffolds with a working load of 750 pounds, no more than 
three men shall be permitted to work at one time. Each workman shall be 
protected by a safety lifebelt attached to a lifeline. The lifeline 
shall be securely attached to substantial members of the structure (not 
scaffold), or to securely rigged lines, which will safely suspend the 
workman in case of a fall.
    (10) Where acid solutions are used, fiber ropes are not permitted 
unless acid-proof.
    (11) Two-point suspension scaffolds shall be securely lashed to the 
building or structure to prevent them from swaying. Window cleaners' 
anchors shall not be used for this purpose.
    (12) The platform of every two-point suspension scaffold shall be 
one of the following types:
    (i) The side stringer of ladder-type platforms shall be clear 
straight-grained spruce or materials of equivalent strength and 
durability. The rungs shall be of straight-grained oak, ash, or hickory, 
at least 1\1/8\ inch in diameter, with seven-eighth inch tenons mortised 
into the side stringers at least seven-eighth inch. The stringers shall 
be tied together with the tie rods not less than one-quarter inch in 
diameter, passing through the stringers and riveted up tight against 
washers on both ends. The flooring strips shall be spaced not more than 
five-eighth inch apart except at the side rails where the space may be 1 
inch. Ladder-type platforms shall be constructed in accordance with 
table D-17.
    (ii) Plank-type platforms shall be composed of not less than nominal 
2- x 8-inch unspliced planks, properly cleated together on the underside 
starting 6 inches from each end; intervals in between shall not exceed 4 
feet. The plank-type platform shall not extend beyond the hangers more 
than 18 inches. A bar or other effective means shall be securely 
fastened to the platform at each end to prevent its slipping off the 
hanger. The span between hangers for plank-type platforms shall not 
exceed 10 feet.
    (iii) Beam platforms shall have side stringers of lumber not less 
than 2 x 6 inches set on edge. The span between hangers shall not exceed 
12 feet when beam platforms are used. The flooring shall be supported on 
2- and 6-inch crossbeams, laid flat and set into the upper edge of the 
stringers with a snug fit, at intervals of not more than 4 feet, 
securely nailed in place. The flooring shall be of 1- x 6-inch material 
properly nailed. Floorboards shall not be spaced more than one-half inch 
apart.

                                 Table D-17--Schedule for Ladder-Type Platforms
----------------------------------------------------------------------------------------------------------------
                                                                       Length of platform (feet)
                                                     -----------------------------------------------------------
                                                          12        14 & 16     18 & 20     22 & 24     28 & 30
----------------------------------------------------------------------------------------------------------------
Side stringers, minimum cross section (finished
 sizes):
  At ends (in.).....................................    1\3/4\ x    1\3/4\ x  1\3/4\ x 3  1\3/4\ x 3    1\3/4\ x
                                                          2\3/4\      2\3/4\                              3\1/2\
  At middle (in.)...................................    1\3/4\ x    1\3/4\ x  1\3/4\ x 4    1\3/4\ x  1\3/4\ x 5
                                                          3\3/4\      3\3/4\                  4\1/4\
Reinforcing strip (minimum) \1\.....................  ..........  ..........  ..........  ..........  ..........
Rungs \2\...........................................  ..........  ..........  ..........  ..........  ..........
Tie rods:
  Number (minimum)..................................           3           4           4           5           6
  Diameter (minimum)................................    \1/4\ in    \1/4\ in    \1/4\ in    \1/4\ in   \1/4\ in.
Flooring, minimum finished size (in.)...............     \1/2\ x     \1/2\ x     \1/2\ x  \1/2\ x \3/    \1/2\ x
                                                          2\3/4\      2\3/4\      2\3/4\          4\      2\3/4\
----------------------------------------------------------------------------------------------------------------
\1\ A \1/8\x\7/8\-in. steel reinforcing strip or its equivalent shall be attached to the side or underside full
  length.
\2\ Rungs shall be 1\1/8\-in. minimum, diameter with at least \7/8\-in. diameter tenons, and the maximum spacing
  shall be 12 in. center to center.

    (h) Stone setters' adjustable multiple-point suspension scaffolds. 
(1) The scaffold shall be capable of sustaining a working load of 25 
pounds per square

[[Page 141]]

foot and shall not be overloaded. Scaffolds shall not be used for 
storage of stone or other heavy materials.
    (2) The hoisting machine and its supports shall be of a type tested 
and listed by a nationally recognized testing laboratory. Refer to 
Sec. 1910.399(a)(77) for definition of listed, and Sec. 1910.7 for 
nationally recognized testing laboratory.
    (3) The platform shall be securely fastened to the hangers by U-
bolts or other equivalent means.
    (4) The scaffold unit shall be suspended from metal outriggers, iron 
brackets, wire rope slings, or iron hooks which will safely support the 
maximum intended load.
    (5) Outriggers when used shall be set with their webs in a vertical 
position, securely anchored to the building or structure and provided 
with stop bolts at each end.
    (6) The scaffold shall be supported by wire rope conforming with 
paragraph (a)(22) of this section, suspended from overhead supports.
    (7) The free ends of the suspension wire ropes shall be equipped 
with proper size thimbles, secured by splicing or other equivalent 
means. The running ends shall be securely attached to the hoisting drum 
and at least four turns of rope shall remain on the drum at all times.
    (8) Guardrails not less than 2 by 4 inches or the equivalent and not 
less than 36 inches or more than 42 inches high, with a mid-rail, when 
required, of 1- by 4-inch lumber or equivalent, and toeboards, shall be 
installed at all open sides on all scaffolds more than 10 feet above the 
ground or floor. Toeboards shall be a minimum of 4 inches in height. 
Wire mesh shall be installed in accordance with paragraph (a)(17) of 
this section.
    (9) When two or more scaffolds are used on a building or structure 
they shall not be bridged one to the other but shall be maintained at 
even height with platforms butting closely.
    (10) Each scaffold shall be installed or relocated in accordance 
with designs and instructions of a registered professional engineer, and 
such installation or relocation shall be supervised by a competent 
designated person.
    (i) Single-point adjustable suspension scaffolds. (1) The 
scaffolding, including power units or manually operated winches, shall 
be a type tested and listed by a nationally recognized testing 
laboratory. Refer to Sec. 1910.399(a)(77) for definition of listed, and 
Sec. 1910.7 for nationally recognized testing laboratory.
    (2) [Reserved]
    (3) All power-operated gears and brakes shall be enclosed.
    (4) In addition to the normal operating brake, all-power driven 
units must have an emergency brake which engages automatically when the 
normal speed of descent is exceeded.
    (5) Guards, mid-rails, and toeboards shall completely enclose the 
cage or basket. Guardrails shall be no less than 2 by 4 inches or the 
equivalent installed no less than 36 inches nor more than 42 inches 
above the platform. Mid-rails shall be 1 by 6 inches or the equivalent, 
installed equidistant between the guardrail and the platform. Toeboards 
shall be a minimum of 4 inches in height.
    (6) The hoisting machines, cables, and equipment shall be regularly 
serviced and inspected after each installation and every 30 days 
thereafter.
    (7) The units may be combined to form a two-point suspension 
scaffold. Such scaffold shall comply with paragraph (g) of this section.
    (8) The supporting cable shall be straight for its entire length, 
and the operator shall not sway the basket and fix the cable to any 
intermediate points to change his original path of travel.
    (9) Equipment shall be maintained and used in accordance with the 
manufacturers' instructions.
    (10) Suspension methods shall conform to applicable provisions of 
paragraphs (f) and (g) of this section.
    (j) Boatswain's chairs. (1) The chair seat shall be not less than 12 
by 24 inches, and of 1-inch thickness. The seat shall be reinforced on 
the underside to prevent the board from splitting.
    (2) The two fiber rope seat slings shall be of \5/8\-inch diameter, 
reeved through the four seat holes so as to cross each other on the 
underside of the seat.

[[Page 142]]

    (3) Seat slings shall be of at least \3/8\-inch wire rope when a 
workman is conducting a heat producing process such as gas or arc 
welding.
    (4) The workman shall be protected by a safety life belt attached to 
a lifeline. The lifeline shall be securely attached to substantial 
members of the structure (not scaffold), or to securely rigged lines, 
which will safely suspend the worker in case of a fall.
    (5) The tackle shall consist of correct size ball bearing or bushed 
blocks and properly spliced \5/8\-inch diameter first-grade manila rope.
    (6) The roof irons, hooks, or the object to which the tackle is 
anchored shall be securely installed. Tiebacks when used shall be 
installed at right angles to the face of the building and securely 
fastened to a chimney.
    (k) Carpenters' bracket scaffolds. (1) The brackets shall consist of 
a triangular wood frame not less than 2 by 3 inches in cross section, or 
of metal of equivalent strength. Each member shall be properly fitted 
and securely joined.
    (2) Each bracket shall be attached to the structure by means of one 
of the following:
    (i) A bolt no less than five-eighths inch in diameter which shall 
extend through the inside of the building wall.
    (ii) A metal stud attachment device.
    (iii) Welding to steel tanks.
    (iv) Hooking over a well-secured and adequately strong supporting 
member.

The brackets shall be spaced no more than 10 feet apart.
    (3) No more than two persons shall occupy any given 10 feet of a 
bracket scaffold at any one time. Tools and materials shall not exceed 
75 pounds in addition to the occupancy.
    (4) The platform shall consist of not less than two 2- by 9-inch 
nominal size planks extending not more than 18 inches or less than 6 
inches beyond each end support.
    (5) Guardrails not less than 2 by 4 inches or the equivalent and not 
less than 36 inches or more than 42 inches high, with a mid-rail, when 
required, of 1- by 4-inch lumber or equivalent, and toeboards, shall be 
installed at all open sides on all scaffolds more than 10 feet above the 
ground or floor. Toeboards shall be a minimum of 4 inches in height. 
Wire mesh shall be installed in accordance with paragraph (a)(17) of 
this section.
    (l) Bricklayers' square scaffolds. (1) The squares shall not exceed 
5 feet in width and 5 feet in height.
    (2) Members shall be not less than those specified in Table D-18.
    (3) The squares shall be reinforced on both sides of each corner 
with 1- by 6-inch gusset pieces. They shall also have braces 1 by 8 
inches on both sides running from center to center of each member, or 
other means to secure equivalent strength and rigidity.
    (4) The squares shall be set not more than 5 feet apart for medium 
duty scaffolds, and not more than 8 feet apart for light duty scaffolds. 
Bracing 1 x 8 inches, extending from the bottom of each square to the 
top of the next square, shall be provided on both front and rear sides 
of the scaffold.

 Table D-18--Minimum Dimensions for Bricklayers' Square Scaffold Members
------------------------------------------------------------------------
                  Members                        Dimensions (inches)
------------------------------------------------------------------------
Bearers or horizontal members..............  2 by 6.
Legs.......................................  2 by 6.
Braces at corners..........................  1 by 6.
Braces diagonally from center frame........  1 by 8.
------------------------------------------------------------------------

    (5) Platform planks shall be at least 2- by 9-inch nominal size. The 
ends of the planks shall overlap the bearers of the squares and each 
plank shall be supported by not less than three squares.
    (6) Bricklayers' square scaffolds shall not exceed three tiers in 
height and shall be so constructed and arranged that one square shall 
rest directly above the other. The upper tiers shall stand on a 
continuous row of planks laid across the next lower tier and be nailed 
down or otherwise secured to prevent displacement.
    (7) Scaffolds shall be level and set upon a firm foundation.
    (m) Horse scaffolds. (1) Horse scaffolds shall not be constructed or 
arranged more than two tiers or 10 feet in height.
    (2) The members of the horses shall be not less than those specified 
in Table D-19.
    (3) Horses shall be spaced not more than 5 feet for medium duty and 
not more than 8 feet for light duty.

[[Page 143]]

    (4) When arranged in tiers, each horse shall be placed directly over 
the horse in the tier below.
    (5) On all scaffolds arranged in tiers, the legs shall be nailed 
down to the planks to prevent displacement or thrust and each tier shall 
be substantially cross braced.

        Table D-19--Minimum Dimensions for Horse Scaffold Members
------------------------------------------------------------------------
                  Members                        Dimensions (inches)
------------------------------------------------------------------------
Horizontal members or bearers..............  3 by 4.
Legs.......................................  1\1/4\ by 4\1/2\.
Longitudinal brace between legs............  1 by 6.
Gusset brace at top of legs................  1 by 8.
Half diagonal braces.......................  1\1/4\ by 4\1/2\.
------------------------------------------------------------------------

    (6) Horses or parts which have become weak or defective shall not be 
used.
    (7) Guardrails not less than 2 by 4 inches or the equivalent and not 
less than 36 inches or more than 42 inches high with a mid-rail, when 
required, of 1- by 4-inch lumber or equivalent and toeboards, shall be 
installed at all open sides on all scaffolds more than 10 feet above the 
ground or floor. Toeboards shall be a minimum of 4 inches in height. 
Wire mesh shall be installed in accordance with paragraph (a)(17) of 
this section.
    (n) Needle beam scaffold. (1) Wood needle beams shall be in 
accordance with paragraph (a) (5) and (9) of this section, and shall be 
not less than 4 by 6 inches in size, with the greater dimension placed 
in a vertical direction. Metal beams or the equivalent conforming to 
paragraph (a) (4) and (8) of this section may be used.
    (2) Ropes or hangers shall be provided for supports. The span 
between supports on the needle beam shall not exceed 10 feet for 4- by 
6-inch timbers. Rope supports shall be equivalent in strength to 1-inch 
diameter first-grade manila rope.
    (3) The ropes shall be attached to the needle beams by a scaffold 
hitch or a properly made eye splice. The loose end of the rope shall be 
tied by a bowline knot or by a round turn and one-half hitch.
    (4) The platform span between the needle beams shall not exceed 8 
feet when using 2-inch scaffold plank. For spans greater than 8 feet, 
platforms shall be designed based on design requirements for the special 
span. The overhang of each end of the platform planks shall be not less 
than 1 foot and not more than 18 inches.
    (5) When one needle beam is higher than the other or when the 
platform is not level the platform shall be secured against slipping.
    (6) All unattached tools, bolts, and nuts used on needle beam 
scaffolds shall be kept in suitable containers.
    (7) One end of a needle beam scaffold may be supported by a 
permanent structural member conforming to paragraphs (a) (4) and (8) of 
this section.
    (8) Each man working on a needle beam scaffold 20 feet or more above 
the ground or floor and working with both hands, shall be protected by a 
safety life belt attached to a lifeline. The lifeline shall be securely 
attached to substantial members of the structure (not scaffold), or to 
securely rigged lines, which will safely suspend the workman in case of 
a fall.
    (o) Plasterers', decorators', and large area scaffolds. (1) 
Plasterers', decorators', lathers', and ceiling workers' inside 
scaffolds shall be constructed in accordance with the general 
requirements set forth for independent wood pole scaffolds.
    (2) Guardrails not less than 2 by 4 inches or the equivalent and not 
less than 36 inches or more than 42 inches high, with a mid-rail, when 
required, of 1- by 4-inch lumber or equivalent, and toeboards, shall be 
installed at all open sides on all scaffolds more than 10 feet above the 
ground or floor. Toeboards shall be a minimum of 4 inches in height. 
Wire mesh shall be installed in accordance with paragraph (a)(17) of 
this section.
    (3) All platform planks shall be laid with the edges close together.
    (4) When independent pole scaffold platforms are erected in 
sections, such sections shall be provided with connecting runways 
equipped with substantial guardrails.
    (p) Interior hung scaffolds.
    (1) [Reserved]
    (2) The suspended steel wire rope shall conform to paragraph (a)(22) 
of this section. Wire may be used providing the strength requirements of

[[Page 144]]

paragraph (a)(22) of this section are met.
    (3) For hanging wood scaffolds, the following minimum nominal size 
material is recommended:
    (i) Supporting bearers 2 by 9 inches on edge.
    (ii) Planking 2 by 9 inches or 2 by 10 inches, with maximum span 7 
feet for heavy duty and 10 feet for light duty or medium duty.
    (4) Steel tube and coupler members may be used for hanging scaffolds 
with both types of scaffold designed to sustain a uniform distributed 
working load up to heavy duty scaffold loads with a safety factor of 
four.
    (5) When a hanging scaffold is supported by means of wire rope, such 
wire rope shall be wrapped at least twice around the supporting members 
and twice around the bearers of the scaffold, with each end of the wire 
rope secured by at least three standard wire-rope clips.
    (6) All overhead supporting members shall be inspected and checked 
for strength before the scaffold is erected.
    (7) Guardrails not less than 2 by 4 inches or the equivalent and not 
less than 36 inches or more than 42 inches high, with a mid-rail, when 
required, of 1- by 4-inch lumber or equivalent, and toeboards, shall be 
installed at all open sides on all scaffolds more than 10 feet above the 
ground or floor. Toeboards shall be a minimum of 4 inches in height. 
Wire mesh shall be installed in accordance with paragraph (a)(17) of 
this section.
    (q) Ladder-jack scaffolds. (1) All ladder-jack scaffolds shall be 
limited to light duty and shall not exceed a height of 20 feet above the 
floor or ground.
    (2) All ladders used in connection with ladder-jack scaffolds shall 
be heavy-duty ladders and shall be designed and constructed in 
accordance with Sec. 1910.25 and Sec. 1910.26.
    (3) The ladder jack shall be so designed and constructed that it 
will bear on the side rails in addition to the ladder rungs, or if 
bearing on rungs only, the bearing area shall be at least 10 inches on 
each rung.
    (4) Ladders used in conjunction with ladder jacks shall be so 
placed, fastened, held, or equipped with devices so as to prevent 
slipping.
    (5) The wood platform planks shall be not less than 2 inches nominal 
in thickness. Both metal and wood platform planks shall overlap the 
bearing surface not less than 12 inches. The span between supports for 
wood shall not exceed 8 feet. Platform width shall be not less than 18 
inches.
    (6) Not more than two persons shall occupy any given 8 feet of any 
ladder-jack scaffold at any one time.
    (r) Window-jack scaffolds. (1) Window-jack scaffolds shall be used 
only for the purpose of working at the window opening through which the 
jack is placed.
    (2) Window jacks shall not be used to support planks placed between 
one window jack and another or for other elements of scaffolding.
    (3) Window-jack scaffolds shall be provided with suitable guardrails 
unless safety belts with lifelines are attached and provided for the 
workman. Window-jack scaffolds shall be used by one man only.
    (s) Roofing brackets. (1) Roofing brackets shall be constructed to 
fit the pitch of the roof.
    (2) Brackets shall be secured in place by nailing in addition to the 
pointed metal projections. The nails shall be driven full length into 
the roof. When rope supports are used, they shall consist of first-grade 
manila of at least three-quarter-inch diameter, or equivalent.
    (3) A substantial catch platform shall be installed below the 
working area of roofs more than 20 feet from the ground to eaves with a 
slope greater than 3 inches in 12 inches without a parapet. In width the 
platform shall extend 2 feet beyond the projection of the eaves and 
shall be provided with a safety rail, mid-rail, and toeboard. This 
provision shall not apply where employees engaged in work upon such 
roofs are protected by a safety belt attached to a lifeline.
    (t) Crawling boards or chicken ladders. (1) Crawling boards shall be 
not less than 10 inches wide and 1 inch thick, having cleats 1 x 1\1/2\ 
inches. The cleats shall be equal in length to the width of the board 
and spaced at equal intervals not to exceed 24 inches. Nails shall be

[[Page 145]]

driven through and clinched on the underside. The crawling board shall 
extend from the ridge pole to the eaves when used in connection with 
roof construction, repair, or maintenance.
    (2) A firmly fastened lifeline of at least three-quarter-inch rope 
shall be strung beside each crawling board for a handhold.
    (3) Crawling boards shall be secured to the roof by means of 
adequate ridge hooks or equivalent effective means.
    (u) Float or ship scaffolds. (1) Float or ship scaffolds shall 
support not more than three men and a few light tools, such as those 
needed for riveting, bolting, and welding. They shall be constructed in 
accordance with paragraphs (u) (2) through (6) of this section, unless 
substitute designs and materials provide equivalent strength, stability, 
and safety.
    (2) The platform shall be not less than 3 feet wide and 6 feet long, 
made of three-quarter-inch plywood, equivalent to American Plywood 
Association Grade B-B, Group I, Exterior.
    (3) Under the platform, there shall be two supporting bearers made 
from 2- x 4-inch, or 1- x 10-inch rough, selected lumber, or better. 
They shall be free of knots or other flaws and project 6 inches beyond 
the platform on both sides. The ends of the platform shall extend about 
6 inches beyond the outer edges of the bearers. Each bearer shall be 
securely fastened to the platform.
    (4) An edging of wood not less than \3/4\ x 1\1/2\ inches, or 
equivalent, shall be placed around all sides of the platform to prevent 
tools from rolling off.
    (5) Supporting ropes shall be 1-inch diameter manila rope or 
equivalent, free from deterioration, chemical damage, flaws, or other 
imperfections. Rope connections shall be such that the platform cannot 
shift or slip. If two ropes are used with each float, each of the two 
supporting ropes shall be hitched around one end of a bearer and pass 
under the platforms to the other end of the bearer where it is hitched 
again, leaving sufficient rope at each end for the supporting ties.
    (6) Each workman shall be protected by a safety lifebelt attached to 
a lifeline. The lifeline shall be securely attached to substantial 
members of the structure (not scaffold), or to securely rigged lines, 
which will safely suspend the workman in case of a fall.
    (v) Scope. This section establishes safety requirements for the 
construction, operation, maintenance, and use of scaffolds used in the 
maintenance of buildings and structures.

[39 FR 23502, June 27, 1974, as amended at 43 FR 49746, Oct. 24, 1978; 
49 FR 5321, Feb. 10, 1984; 53 FR 12121, Apr. 12, 1988]