[Title 46 CFR 116.610]
[Code of Federal Regulations (annual edition) - October 1, 1996 Edition]
[Title 46 - SHIPPING]
[Chapter I - COAST GUARD, DEPARTMENT OF]
[Subchapter K - SMALL PASSENGER VESSELS CARRYING MORE THAN 150 PASSENGERS]
[Part 116 - CONSTRUCTION AND ARRANGEMENT]
[Subpart F - Ventilation]
[Sec. 116.610 - Ventilation ducts.]
[From the U.S. Government Publishing Office]




  46
  SHIPPING
  4
  1996-10-01
  1996-10-01
  false
  Ventilation ducts.
  116.610
  Sec. 116.610
  
    SHIPPING
    COAST GUARD, DEPARTMENT OF
    SMALL PASSENGER VESSELS CARRYING MORE THAN 150 PASSENGERS
    CONSTRUCTION AND ARRANGEMENT
    Ventilation
  


Sec. 116.610  Ventilation ducts.

    (a) For the purposes of this section, a ventilation duct includes 
any type of piping, chamber, or conduit used for ventilation.
    (b) A ventilation duct, and materials incidental to its 
installation, must be made of noncombustible material.
    (c) Combustibles and other foreign materials are not allowed within 
ventilation ducts. However, metal piping and electrical wiring installed 
in a metal protective enclosure may be installed within ventilation 
ducts, provided that the piping or the wiring does not interfere with 
the operation of fire dampers. Electrical wiring and piping may not be 
installed in an exhaust duct over a frying vat or grill.
    (d) Suitable means, such as a manual damper, automatic damper, or 
vent cover, must be provided in an accessible location outside the space 
served by the ventilation duct for shutting off the passage of air 
through the ventilation duct in the event of fire.
    (e) A ventilation duct must not serve more than one main vertical 
zone; penetrations of main vertical zones must be minimized.
    (f) A ventilation duct penetrating an A-Class or B-Class fire 
control boundary must meet the following requirements:
    (1) A ventilation duct must meet the same requirements relative to 
the passage of smoke and flame as the fire control boundary penetrated;
    (2) A steel duct penetrating an A-Class fire control boundary must 
be of at least 11 USSG, and a steel duct penetrating a B-Class bulkhead 
or deck must be of at least 16 USSG;
    (3) A duct that is not steel must be fitted with a steel sleeve at 
each A-Class or B-Class fire control boundary penetrated. The sleeves 
must extend at least 455 millimeters (18 inches) on each side of the 
penetration and be of the same thickness required for steel ducts;
    (4) A duct penetrating a main vertical zone bulkhead must be fitted 
with an automatic fire damper at the main vertical zone bulkhead;
    (5) A duct penetrating an A-Class fire control boundary and opening 
into a space formed by that boundary must be equipped with a fire 
damper;

[[Page 342]]

    (6) A steel duct that penetrates an A-Class fire control boundary 
other than a main vertical zone bulkhead, and does not open within the 
space formed by the boundary need not be fitted with a fire damper 
provided the duct is at least 11 USSG throughout that space;
    (7) A duct penetrating an insulated fire control boundary must be 
fitted with insulation of the same type and thickness as the boundary 
penetrated for a distance of at least 305 millimeters (12 inches) on the 
insulated side of the boundary. A fire damper blade need not be 
insulated; and
    (8) Ducts serving cargo spaces, machinery spaces, or vehicles spaces 
must be fitted with automatic fire dampers.
    (g) Fire dampers, where required by this section, must comply with 
the following requirements;
    (1) A fire damper and casing must be at least 11 USSG and not more 
than 3.2 millimeters (0.125 inch) gap between the blade and casing;
    (2) A fire damper must close against the draft in the duct and be 
accessible for periodic inspection by means of a hinged or bolted plate 
in the duct and surrounding bulkhead or deck, if fitted;
    (3) Fire damper springs, blades, and hinges must be of stainless 
steel construction or of steel suitably coated to prevent corrosion;
    (4) Fire dampers must be capable of manual operation from outside 
the space served, be fitted with an indicator showing whether the damper 
is open or closed, and be marked with red letters of at least 12.7 
millimeters (0.5 inches) in height stating ``VENTILATION FIRE DAMPER''; 
and
    (5) An automatic fire damper must meet the above requirements and 
must be designed to operate at 74 deg.C (165 deg.F) for normal locations 
and approximately 100 deg.C (212 deg.F) for locations such as galleys.
    (h) A ventilation duct serving a stairtower must not serve another 
space.
    (i) A stairway or a stairtower must not serve as an air return for 
another space.
    (j) A duct in a bulkhead or overhead designed for the passage of air 
from one space to another (i.e., a ``jumper duct'') is prohibited.
    (k) The use of concealed spaces as return ventilation plenums or 
ducts is prohibited. Ventilation air return must be by ducts.